Shortening Of "Maintenance Cycle" And "Replacement Cycle" Needs To Be Considered In Following Situations - Daikin RXYCQ8A7Y1B Operation Manual

Vrv classic system air conditioner
Hide thumbs Also See for RXYCQ8A7Y1B:
Table of Contents

Advertisement

WARNING
Do not modify, disassemble, remove, reinstall or
repair the unit yourself as incorrect dismantling or
installation may cause an electric shock or fire.
Contact your dealer.
In case of accidental refrigerant leaks, make sure
there are no naked flames. The refrigerant itself is
entirely safe, non-toxic and non-combustible, but it will
generate toxic gas when it accidentally leaks into a
room where combustible air from fan heaters, gas
cookers, etc. ... is present.
Always have qualified service personnel confirm that
the point of leakage has been repaired or corrected
before resuming operation.
Recommended inspection and maintenance cycles
Be aware that the mentioned maintenance and replacement cycles
do not relate to the warranty period of the components.
Table 1: "Inspection Cycle" and "Maintenance Cycle" list
Component
Electric motor
PCB
Heat exchanger
Sensor (thermistor, etc.)
Remote controller and switches
Drain pan
Expansion valve
Electromagnetic valve
Table 1 assumes the following conditions of use:
1.
Normal use without frequent starting and stopping of the unit.
Depending on the model, we recommend not starting and
stopping the machine more than 6 times/hour.
2.
Operation of the unit is assumed to be 10 hours/day and 2,500
hours/year.
NOTE
1.
Table 1 indicates main components.
Refer to your maintenance and inspection contract
for more details.
2.
Table 1 indicates recommended intervals of
maintenance cycles. However, in order to keep the
unit operational as long as possible, maintenance
work may be required sooner.
Recommended
appropriate maintenance design in terms of
budgetting maintenance and inspection fees.
Depending on the content of the maintenance and
inspection contract, inspection and maintenance
cycles may in reality be shorter than listed.
Operation manual
8
Maintenance cycle
(replacements and/
Inspection cycle
or repairs)
20,000 hours
25,000 hours
5 years
5 years
1 year
25,000 hours
8 years
20,000 hours
20,000 hours
intervals
can
be
used
12.2. Shortening of "maintenance cycle" and
"replacement cycle" needs to be considered in
following situations
The unit is used in locations where:
1.
heat and humidity fluctuate out of the ordinary
2.
power fluctuation is high (voltage, frequency, wave distortion,
etc.)
(The unit cannot be used if power fluctuation is outside the
allowable range.)
3.
bumps and vibrations are frequent
4.
dust, salt, harmful gas or oil mist such as sulfurous acid and
hydrogen sulfide may be present in the air
5.
the machine is started and stopped frequently or operation time
is long (sites with 24 hour air-conditioning).
Recommended replacement cycle of wear parts
Table 2: "Replacement Cycle" list
Component
Air filter
High efficiency filter (Optional)
Fuse
Crankcase heater
NOTE
1.
Table 2 indicates main components.
Refer to your maintenance and inspection contract
for more details.
2.
Table 2 indicates recommended intervals of
replacement cycles. However, in order to keep the
unit operational as long as possible, maintenance
work may be required sooner.
Recommended
appropriate maintenance design in terms of
budgetting maintenance and inspection fees.
Contact your dealer for details.
Damage due to taking apart or cleaning interiors of
NOTE
units by anyone other than our authorised dealers may
not be included in the warranty.
Moving and discarding the unit
■ Contact your dealer for removing and reinstalling the total
unit. Moving units requires technical expertise.
■ This unit uses hydrofluorocarbon.
for
Contact your dealer when discarding this unit. It is required
by law to collect, transport and discard the refrigerant in
accordance with the "hydrofluorocarbon collection and
destruction" regulations.
Maintenance cycle
(replacements and/
Inspection cycle
or repairs)
5 years
1 year
1 year
10 years
8 years
intervals
can
be
used
RXYCQ8~20A7Y1B
VRV Classic System air conditioner
4P327539-1 — 2012.08
for

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents