QuickSpecs
Configuration
Power Protection
Power Protection
Power Protection
Power Protection
Runtimes
Runtimes
Runtimes
Runtimes
The UPS will provide battery backup to allow for a graceful shutdown in the event of a power failure. Typical runtime on the
APC SL20KFB2 Silcon 3 Phase UPS varies with the kW rating and the load. The APC SL20KFB2 UPS provides a typical
runtime of 36.7 minutes at half load and 10.7 at full load. If additional run time is needed please contact your APC
representative
Power Conditioning
Power Conditioning
Power Conditioning
Power Conditioning
The APC SL20KFB2 provides unparalleled power conditioning with its Delta-Conversion on-line double conversion
technology. This is especially helpful in regions were power is unstable.
Continuous Power during Short Interruptions of Input Power
Continuous Power during Short Interruptions of Input Power
Continuous Power during Short Interruptions of Input Power
Continuous Power during Short Interruptions of Input Power
The APC SL20KFB2 will provide battery backup to allow for continuous power to the connected equipment in the event of a
brief interruption in the input power to the UPS. Transaction activity will continue during brief power outage periods as long
as qualified UPS units are used to provide backup power to the SPU, the Expansion Modules, and all disk and disk array
products.
UPS Configuration Guidelines
UPS Configuration Guidelines
UPS Configuration Guidelines
UPS Configuration Guidelines
In general, the sum of the "Watt rating for UPS sizing" for all of the connected equipment should not exceed the watt rating
of the UPS from which they all draw power. In previous configuration guides, this variable was called the "VA rating for UPS
sizing." With Unity Power Factor, the Watt rating was the same as the kVA rating, so it didn't matter which one we used. VA is
calculated by multiplying the voltage times the current. Watts, which is a measurement of true power, may be less than VA if
the current and voltage are not in phase. APC SL20KFB2 has Unity Power Factory correction, so the kW rating equals the
kVA rating. Be sure to add in the needs for the other peripherals and connected equipment. When sizing the UPS, allow for
future growth as well. If the configuration guide or data sheet of the equipment you want to protect gives a VA rating, use
this as the watt rating. If the UPS does not provide enough power for the additional devices such as system console and mass
storage devices, additional UPSs may be required.
Superdome
Superdome
Superdome
Superdome
The only qualified UPS available for use with Superdome is the APC SL20KFB2 Silcon 3 Phase 20-kW UPS.
The APC SL20KFB2 can provide power protection for the SPU and peripherals. If the system console and primary mass
storage devices also require power protection (which is highly recommended) they may require one or more additional UPSs
depending on the total Watts. Make sure that the total watts do not exceed the UPS's voltage rating.
Integration/Installation
Integration/Installation
Integration/Installation
Integration/Installation
The APC SL20KFB2 includes both field integration start up service and next day on-site service for one year provide by APC.
Power Connections with the APC SL20KFB2
Power Connections with the APC SL20KFB2
Power Connections with the APC SL20KFB2
Power Connections with the APC SL20KFB2
Communications Connections
Communications Connections
Communications Connections
Communications Connections
A DB-25 RS-232 Contact Closure connection is standard on all APC SL20KFB2 UPS. A WEB/SNMP card is also included.
Power Management
Power Management
Power Management
Power Management
Product Number
Product Number
Product Number
Product Number
Watts
Watts
Watts
Watts
SL20KFB2
20 kW
Description
Description
Description
Description
Network interface cards that provide standards-based remote management of UPSs
General Features
General Features
General Features
General Features
Boot-P support, Built-in Web/SNMP management, Event logging, Flash Upgradeable,
MD5 Authentication Security, Password Security, SNMP Management, Telnet Management,
Web Management
Includes
Includes
Includes
Includes
CD with software, User Manual
Documentation
Documentation
Documentation
Documentation
User Manual
Installation Guide
DA - 11717
North America — Version 15 — January 3, 2005
HP Integrity Superdome Servers: 16-socket, 32-
HP Integrity Superdome Servers: 16-socket, 32-
HP Integrity Superdome Servers: 16-socket, 32-
HP Integrity Superdome Servers: 16-socket, 32-
NOM Out
NOM Out
NOM Out
NOM Out
Output Receptacles Input Receptacles
Output Receptacles
Output Receptacles
Output Receptacles
115/200 3PH, 120/208
Hardwire
3PH, 127/220 3PHV
socket, and 64-socket
socket, and 64-socket
socket, and 64-socket
socket, and 64-socket
Input Receptacles
Input Receptacles
Input Receptacles
Hardwire
Page 25