HP Integrity Superdome 16-socket Specification page 22

Integrity superdome servers
Hide thumbs Also See for Integrity Superdome 16-socket:

Advertisement

QuickSpecs
Configuration
a. In line connector is available from HP by purchasing A6440A, Option 401.
b. Panel mount receptacles must be purchased by the customer from a local Mennekes supplier.
NOTE: A qualified electrician must wire the PDCA in line connector to site power using copper wire and in compliance
NOTE:
NOTE:
NOTE:
with all local codes.
Input Requirements
Input Requirements
Input Requirements
Input Requirements
Reference the Site Preparation Guide for detailed power configuration requirements.
Cooling Requirements
Cooling Requirements
Cooling Requirements
Cooling Requirements
DataCool is a custom engineered overhead solution for both new data center construction and for data room upgrades for
high heat loads. It is based on Liebert's TeleCool product, which has been installed in 600 telecommunications equipment
PDCA Product
PDCA Product
PDCA Product
PDCA Product
Attached Power
Attached Power
Attached Power
Attached Power
Number
Number
Number
Number
Cord
Cord
Cord
Cord
A5800A Option 006 OLFLEX 190 (PN
600804), four-
conductor, 6-AWG
2
(16 mm
), 600- Volt,
60-Amp, 90- degree
C, UL, and CSA
approved, conforms
to CE directives
GN/YW ground wire.
Requirements
Requirements
Requirements
Requirements
Nominal Input Voltage (VAC rms)
Input Voltage Range (VAC rms)
Frequency Range (Hz)
Number of Phases
Maximum Input Current (A rms), 3-
Phase 4-wire
Maximum Inrush Current (A peak)
Circuit Breaker Rating (A),
3-Phase 4-wire
Power Factor Correction
Ground Leakage Current (mA)
The cooling system in Superdome was designed to maintain reliable operation of the system in the specified
environment. In addition, the system is designed to provide redundant cooling (i.e. N+1 fans and blowers) that
allows all of the cooling components to be "hot swapped."
Superdome was designed to operate in all data center environments with any traditional room cooling scheme (i.e.
raised floor environments) but in some cases where data centers have previously installed high power density systems,
alternative cooling solutions may need to be explored by the customer. HP has teamed with Liebert to develop an
innovative data room cooling solution called DataCool. DataCool is a patented overhead climate system utilizing
fluid based cooling coils and localized blowers capable of cooling heat loads of several hundred watts per square
foot. Some of DataCool's highlights are listed below:
Liebert has filed for several patents on DataCool
DataCool, based on Liebert's TeleCool, is an innovative approach to data room cooling
Liquid cooling heat exchangers provide distributed cooling at the point of use
Delivers even cooling throughout the data center preventing hot spots
Capable of high heat removal rates (500 W per square foot)
Floor space occupied by traditional cooling systems becomes available for revenue generating equipment.
Enables cooling upgrades when installed in data rooms equipped with raised floor cooling
DA - 11717
North America — Version 15 — January 3, 2005
HP Integrity Superdome Servers: 16-socket, 32-
HP Integrity Superdome Servers: 16-socket, 32-
HP Integrity Superdome Servers: 16-socket, 32-
HP Integrity Superdome Servers: 16-socket, 32-
Attached Plug
Attached Plug
Attached Plug
Attached Plug
In Line Connector
In Line Connector
In Line Connector
In Line Connector
Mennekes ME 460P9
Mennekes ME 460C9 3-
3-phase, 4-wire, 60-
phase,
Amp, 250-Volt, UL-
4-wire, 60-amp, 250-Volt,
approved. Color
UL-approved. Color blue,
blue, IEC 309-1, IEC
IEC 309-1, IEC 309-1,
309-1, grounded at
grounded at 9:00 o'clock.
3:00 o'clock.
Value
Value
Value
Value
200/208/220/230/240
200-240
50/60
3
40
90
45 A
0.95 minimum
>3.5 mA, with 6 BPSs installed
socket, and 64-socket
socket, and 64-socket
socket, and 64-socket
socket, and 64-socket
Customer Provided Part
Customer Provided Part
Customer Provided Part
Customer Provided Part
Panel Mount
Panel Mount
Panel Mount
Panel Mount
Receptacle
Receptacle
Receptacle
Receptacle
Mennekes ME 460R9 3
phase,
4-wire, 60-amp, 250-Volt,
UL-approved. Color blue,
IEC 309-1, IEC 309-1,
a
grounded at 9:00 o'clock.
Conditions/Comments
Conditions/Comments
Conditions/Comments
Conditions/Comments
Auto selecting. Measure at input
terminals
3-phase 4-wire with power cord
3-phase source with a source voltage of
either 208 VAC or 230 VAC measured
phase to phase
Per phase
Warning label applied to the PDCA at
the AC Mains input
b
Page 22