4.6

Battery management

Maximum battery life and reliability are obtained by the following features:
Quick battery test
The quick battery test checks whether the batteries and their wiring are healthy. If a quick battery test shows
that the batteries are close to being worn out, a 'replace battery' alarm will be generated (see 4.4.8). The
batteries must be replaced as soon as possible (see 7.4).
Automatic battery test
The VH Series UPS conducts periodic automatic battery tests:
• 5 hours after manual switch-on
• 5 hours after return of mains following any power failure, and
• 30 days from the last battery test
Manual battery test
A quick battery test can be initiated manually
-
either via the front panel, by pressing pushbutton 'I' for 5 seconds during normal operation,
-
or via UPS monitoring software. For details please refer to the manual of your software.
NOTE
If the test is started manually immediately after installation or after a power failure, the UPS
may generate a false 'replace battery' alarm as the batteries have been (partly) discharged
during transport/storage or during the power failure.
Deep battery test
A deep battery test, to be initiated through the UPS software via the USB communication port, checks the
actual battery capacity in order to ensure accurate runtime prediction. During a deep battery test the
batteries will be discharged until 'battery low' alarm level. Please note that immediately after a deep battery
test the expected runtime is very short: allow the UPS to recharge its batteries. For details please refer to the
manual of your UPS software.
Temperature compensated battery charging
This feature adjusts the battery charge voltage according to the ambient temperature. As a result poor
charging of the batteries under low temperature conditions and overcharging of the batteries under high
temperature conditions are avoided.
Load dependent battery-end-voltage
The allowable final battery voltage depends on the discharge current: the higher the current, the lower the
'end-of-discharge' battery voltage. In this way maximum battery capacity is obtained without
overdischarging. Overdischarging would result in shortened service life and failure to recover normal capacity.
Automatic boost charge
This feature reduces the battery recharge time considerably: totally depleted batteries will be recharged to
90% in approx. 1.5 hours, provided that discharging took place at 100% load.