Injector Size Chart; Minimum Flame Adjustment - Bosch PHW206FAU User Instruction & Installation Manual

For use with natural gas and universal lpg
Table of Contents

Advertisement

Minimum flame adjustment.

1 T urn the control knob to minimum.
2 Remove the control knob from the valve spindle.
9
Refer Fig.
.
Apply pressure with the tip of the screwdriver to
3
release the thread toward the tap's adjusting screw.
Refer Fig.10.
4 The adjustment screw is positioned at the rear lower
section of the valve.
5 To adjust the minimum flame for N.G. replace the
control knob onto the spindle, light the gas and turn
the control knob to the small flame position. Screw
the adjustment screw anti-clockwise to estabilish a
minimum stable flame position. The flame should
remain alight and not burn back to the injector when
the valve is turned quickcly from 'Full On' to the
"Minimum flame" position and back a few times.
To adjust the minimum flame position for ULPG the
screw must be fully tightened down clockwise.
R
6
efit the control knob. Never dismount the
valve shaft: in the event of damage, change the entire
valve.
9
10
12