Automatic Transfer Operation; Sequence Of Automatic Operation; Manual Transfer Operation; Transfer To Generator Power Source - Generac Power Systems 04758-2, 04759-2, 04760-2 Installation And Owner's Manual

Generac air-cooled automatic standby generator installation and owner's manual
Hide thumbs Also See for 04758-2, 04759-2, 04760-2:
Table of Contents

Advertisement

3.3
AUTOMATIC TRANSFER
OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are
set to their "Utility" position, i.e., loads connected
to the utility power source (Figure 3.2).
2. Be sure that normal utility power source voltage
is available to transfer switch terminal lugs N1
and N2.
3. Set the generator's AUTO/OFF/MANUAL switch to
AUTO.
4. Set the generator's main circuit breaker to its ON
(or closed) position.
With the preceding steps complete, the generator will
start automatically when utility source voltage drops
below a preset level. After the unit starts, loads are
transferred to the standby power source. Refer to
Section 3.4, "Sequence of Automatic Operation."
3.4
SEQUENCE OF AUTOMATIC
OPERATION
The generator's control panel houses a control logic
circuit board. This board constantly monitors utility
power source voltage. Should that voltage drop below
a preset level, circuit board action will signal the
engine to crank and start. After the engine starts, the
circuit board signals the transfer switch to activate
and connect load circuits to the standby power sup-
ply (load terminal lugs T1/T2 connect to terminal
lugs E1/E2).
Upon restoration of utility source voltage above a pre-
set level, generator circuit board action signals the
transfer switch to transfer loads back to that power
supply. After retransfer, the engine is signalled to shut
down.
The actual sequence of operation is controlled by
sensors and timers on a control logic circuit board,
as follows:
A. Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 70 per-
cent of the nominal supply voltage, the sensor
energizes a 15-second timer.
• Once the timer has expired, the engine will crank
and start.
B. Engine Warm-up Time Delay
• This mechanism lets the engine warm up for
about 10 seconds before the load is transferred
to a standby source.
C.Standby Voltage Sensor
• This sensor monitors generator AC output volt-
age. When the voltage has reached 50 percent of
the nominal rated voltage, transfer to standby
can occur.
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
D.Utility Voltage Pickup Sensor
• This sensor monitors utility power supply volt-
E.Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action
• Retransfer to utility power source then occurs.
F . Engine Cool-down Timer
• When the load is transferred back to utility power
• The timer will run for about one minute, and the
3.5
To start the generator and activate the transfer switch
manually, proceed as follows:
1. Set the generator's main circuit breaker to its
2. Set the generator's AUTO/OFF/MANUAL switch
3. Turn OFF the utility power supply to the transfer
4. Use the manual transfer handle inside the trans-
5. To crank and start the engine, set the AUTO/OFF/
6. Let the engine stabilize and warm up for a few
7. Set the generator's main circuit breaker to its ON
Section 3 — Operation
age. When that voltage is restored to above 70
percent of the nominal source voltage, a retrans-
fer time delay starts timing.
de-energizes the transfer relay in the transfer
switch.
source, the engine cool-down timer starts timing.
generator will then shut down.

MANUAL TRANSFER OPERATION

3.5.1 TRANSFER TO GENERATOR
POWER SOURCE
OFF (or open) position.
to OFF .
switch using the means provided (such as a
utility main line circuit breaker).
DANGER
Do not attempt to activate the transfer switch
manually until all power voltage supplies to
the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.
fer switch to move the main contacts to their
"Standby" position, i.e., loads connected to the
standby power source (Figure 3.2).
MANUAL switch to MANUAL.
minutes.
(or closed) position. The standby power source
now powers the loads.