Out Of Service Procedure; Removal From Service; Return To Service; Fuel Pipe Sizing - Generac Power Systems 004912-0, 004912-1, 004913-0, 004913-1 Owner's Manual

Liquid-cooled, prepackaged standby generators (15 kw lp/15 kw natural gas) 120/240v single-phase w/ 100 amp transfer switch; (25 kw lp/25 kw natural gas) 120/240v single-phase w/ 200 amp transfer switch
Table of Contents

Advertisement

1. The base frame of the unit contains an optional
fuel inlet location that is capped at the factory.
Check that it is secured in place. The same
applies for any access ports in the roof of the
enclosure. If any of these caps are missing,
contact a Generac Authorized Dealer.
2. Inside the generator set, the chance of rodent
entry into the control panel is greatly reduced by
the inclusion of adjustable wire connectors.
Check that the wire connector screws are tight,
thus closing off any gap between the access holes
and the wires.
4.7

OUT OF SERVICE PROCEDURE

4.7.1

REMOVAL FROM SERVICE

If the generator cannot exercise every seven days, and
it is to be out of service longer than 90 days, prepare
the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line
and allow the unit to shut down.
3. Once the unit has shut down, it will signal a fault
on the control panel.
4. Set the Auto/Off/Manual switch to OFF and turn
off the utility power to the transfer switch.
5. While the engine is still warm from running,
drain the oil completely. Refill the crankcase with
SAE 15W-40 oil having API Service Class SD, SE
or SF . (See "Engine Oil Recommendations" in
Section 1.14)
6. Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
7. Remove the spark plug(s) and spray fogging agent
into the spark plug(s) threaded openings.
Reinstall and tighten the spark plug(s).
8. Remove the battery and store it in a cool, dry
room on a wooden board. Never store the battery
on any concrete or earthen floor.
9. Clean and wipe the entire generator.
4.7.2

RETURN TO SERVICE

To return the unit to service after storage, proceed
as follows:
1. Verify that utility power is turned off to the
transfer switch and that the Auto/Off/Manual
switch is set to OFF .
2. Check the tag on the engine for oil viscosity and
classification. Verify that the correct recom-
mended oil is used in engine. See Section 1.14. If
necessary, drain and refill with the proper oil.
Centurion Liquid-cooled 15 kW and 25 kW Generators
3. Check the battery. Fill all cells to the proper level
with deionized water. DO NOT USE TAP WATER
IN THE BATTERY. Remove the battery before
charging. Recharge the battery to 100 percent
state of charge, or, if defective, replace the battery
with a 12-volt DC Group 26/26R battery rated for
75 amp hours 525 CCA minimum @ 0° F .
4. Clean and wipe the entire generator.
5. Reconnect the battery. Observe battery polarity.
Damage may occur if the battery is connected
incorrectly.
6. Open the fuel shutoff valve.
7. Start the unit by moving the Auto/Off/Manual
switch to MANUAL. Allow the unit to warm up
thoroughly.
8. Stop the unit and set the Auto/Off/Manual switch
to AUTO.
9. Turn on the utility power to the transfer switch.
10. The generator is now ready for service.
4.8
Refer to chart for proper sizing of fuel supply piping.
Insufficient fuel pipe size can cause hard starting,
poor engine performance and inability to carry load.
Length of Pipe
in Feet
* Consumption in Cubic Feet Per Hour.
Part Name
Oil Filter
Radiator Cap
Air Cleaner
Spark Plug
Section 4 — Maintenance

FUEL PIPE SIZING

NG and LP Vapor Pipe Sizing Chart:
Iron Pipe Size (IPS Inches)
½"
¾"
15
76
172
30
52
120
45
43
99
60
38
86
75
77
90
70
105
65
120
150
180
210
240
270
300
450
600
PERIODIC REPLACEMENT PARTS
Generac's Part Number
# 0A45310244
# 046627
# 059402
# 0A45310275
Generac
®
Power Systems, Inc. 19
1"
1 ¼"
1 ½"
2"
345
750
1,220
2,480
241
535
850
1,780
199
435
700
1,475
173
380
610
1,290
155
345
545
1,120
141
310
490
1,000
131
285
450
920
120
270
420
860
109
242
380
780
100
225
350
720
92
205
320
660
190
300
620
178
285
580
170
270
545
140
226
450
119
192
390