Return To Service; Attention After Submersion; Corrosion Protection; Out Of Service Procedure - Generac Power Systems 6055 Owner's Manual

20kw
Hide thumbs Also See for 6055:
Table of Contents

Advertisement

Maintenance
Install the AVR fan.
10.
Connect 4-pin connector to AVR. Press pin and socket halves together until external latch engages.
11.
Install AVR filter housing so the bottom drops into the slots and ensuring that the rubber boot is completely around
12.
the fan opening. Install screw to fasten AVR filter housing to back panel and torque to 50-96 in-lbs (6-11 Nm).
4.8 — Return to Service
Install front access panel.
1.
Install T1 fuse in transfer switch.
2.
Pull up rubber flap covering fuse holder and install 7.5 amp fuse.
3.
Follow Install Wizard instructions using LCD screen and control pad.
4.
Move the Generator Disconnect Circuit Breaker switch to the ON (Closed) position.
5.
Press AUTO on the control pad. A green LED illuminates to confirm that the system is in the AUTO mode.
6.
Close lid. Lock left and right side locks.
7.
4.9 — Attention After Submersion
If the generator has been submerged in water, it MUST NOT be started and operated. Following any submersion in
water, have a Dealer thoroughly clean, dry, and inspect the generator. If the structure (home) has been flooded, it
should be inspected by a certified electrician to ensure there won't be any electrical problems during generator opera-
tion or when utility power is returned.
4.10 — Corrosion Protection
Periodically wash and wax the enclosure using automotive type products. Frequent washing is recommended in salt
water/coastal areas. Spray engine linkages with a light oil such as WD-40.
4.11 — Out of Service Procedure
If the generator cannot be exercised every seven days and will be out of service longer than 90 days, prepare the gen-
erator for storage.
4.11.1— Remove For Storage
Press MANUAL on the control pad to start the engine. A blue LED illuminates to confirm that the system is in the
1.
MANUAL mode.
32
Pivot Ball
Stud
Jam Nut
Figure 4-7. Check/Adjust Valve Clearance
Rocker
Arm
Valve
Stem
Synergy Automatic Standby Generator Owner's Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents