Summary of Contents for Generac Power Systems 0043736, 0046265
Page 1
Owner’s Manual Liquid-cooled, Prepackaged Standby Generators Models: 0043736 (40 kW/Single-phase w/ 200 Amp Transfer Switch) 0046265 (40 kW/Single-phase w/ 200 Amp Transfer Switch California ® POWER SYSTEMS, INC. Emissions) ® Not intended for use in critical life support applications. ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION!! DEADLY EXHAUST FUMES.
INTRODUCTION Thank you for purchasing the Guardian product line by Generac Power Systems. This model is a compact, high performance, liquid-cooled, engine-driven gen- erator designed to automatically supply electrical power to operate critical loads during a utility power failure. This unit is factory installed in an all-weather, metal enclosure that is intended exclusively for outdoor installation.
Generac ® Power Systems, Inc. GENERAL HAZARDS • For safety reasons, Generac recommends that the installation, initial start-up and maintenance of this equipment is carried out by a Generac/Guardian Authorized Dealer. • Installation, operation, servicing and repair of this (and related) equipment must always comply with applicable codes, standards, laws and regulations.
Keep the area surrounding the generator clean and free from debris. • Generac generator sets may operate using one of sev- eral types of fuels. All fuel types are potentially FLAM- MABLE and/or EXPLOSIVE and should be handled with care.
Each single winding can supply a 120VAC, 60-Hertz output. When Generac ® Power Systems, Inc. the two windings are connected in series, a 240VAC, 60- Hertz output results.
The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. Generac uses an AGC fuse rated at 15 amps. 1.8.1 GENERATOR Models ...0043736, 0046265...
Cooling System Capacity ...4.5 U.S. gallons (17 L) Recommended Coolant ...Use a 50-50 mixture of Fuel Consumption Natural Gas ...720 cfh LP Gas ...288 cfh/7.9gph Generac ® Power Systems, Inc. FUEL REQUIREMENTS AND RECOMMENDATIONS With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liquid fuel in the storage tank.
Using any high silicate antifreeze boosters or additives also will cause overheating. Generac also recommends that any soluble oil inhibitor NOT be used for this equip- ment. Section 1 — General Information Guardian Liquid-cooled 40 kW Generator 1.12 EMISSIONS CONTROL SYSTEM...
Connecting this generator to an electrical system normally supplied by an electric utility shall be by means of a transfer switch (such as the Generac “Pre-packaged” type transfer switch), so as to isolate the electric system from the utility distribution system when the generator is operating. Failure to isolate the electric system by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.
Figure 2.2 – Generator Grounding Lug (typical) GENERATOR AC NEUTRAL CONNECTIONS Generac uses an UNGROUNDED AC neutral. Grounding is recommended only at the main service entrance. TRANSFER SWITCH START SIGNAL CONNECTIONS 2.6.1 PRE-PACKAGED TYPE SWITCH...
The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles. 10 Generac ® Power Systems, Inc. 2.7.1 VENTED BATTERIES The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes.
On acoustic units, cap plugs also are needed to stay within noise specification limits. Section 1.8, 1.10, “Engine Section 1.8, Section 2 — Installation Figure 2.3 - Base Frame Cap Plugs Generac ® Power Systems, Inc. 11...
Battery voltage should read approximately12.5 to 14.5 volts DC. A low battery voltage indicates the battery is discharging. 12 Generac ® Power Systems, Inc. 3.1.5 HOURMETER This indicates the time the engine-generator has operat- ed, in hours and tenths of hours.
• The timer will run for about one minute, and the generator will then shut down. ENGINE HEATER This Generac standby generator comes equipped with a block heater (Figure 3.2, page 14) that is similar to the block heaters used in automotive applications. The block heater must be connected to a customer supplied 120V AC circuit.
• Place a sign on the generator’s control panel and on the transfer switch that indicates the day and time the generator will be exercising. 14 Generac ® Power Systems, Inc. If the battery terminals are disconnected or the con-...
8. Check the oil level after checking for leaks to ensure that the oil is filled to the proper level. To replace the engine air cleaner, (Generac part num- ber 0A4637), remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover.
4.5.1 BATTERY REPLACEMENT Generac uses a Group 27F vented type battery that has 600 CCA @ 0º F . Generac’s part number is 058665. NOTE: The BCI number should be located directly on the battery.
Once each year, have the generator cleaned and inspect- ed by a Generac/Guardian Authorized Dealer. Service technicians will use dry, low pressure air to clean inter- nal windings. Parts inside the control console should be cleaned and inspected at this time as well.
8. Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor. 9. Clean and wipe the entire generator. 18 Generac ® Power Systems, Inc. 4.11.2 RETURN TO SERVICE...
4.12 SERVICE SCHEDULE ATTENTION: It is recommended that all service work be performed by the nearest Generac/Guardian Authorized Dealer. SYSTEM/COMPONENT X = Action R = Replace/Adjust as Needed * = Notify Dealer if Repair is Needed. FUEL Fuel lines and connections*...
There is no AC output from the generator. There is no transfer to STANDBY after UTILITY source failure. *Contact the nearest Generac/Guardian Authorized Dealer for assistance. 20 Generac ® Power Systems, Inc. CAUSE 1. Fuse blown 2. Loose, corroded or defective battery cables 3.
Section 8 — Exploded Views and Parts Lists Guardian Liquid-cooled 40 kW Generators Mounting Base - Drawing No. 0E6976 BLACK 30 Generac ® Power Systems, Inc. TO STARTER SOLENOID 12 19 To Oil Drain On Oil Pan.
Page 33
WASHER LOCK M6-1/4 NUT HEX 1/4-20 STEEL SCREW HHC M8-1.25 X 60 G8.8 FT NUT LOCK FL M8-1.25 BATT 12VDC 90-AH 27F HOLD DOWN BATTERY NUT LOCK HEX M8-1.25 NYL INSRT BOOT BATTERY CABLE Generac ® Power Systems, Inc. 31...
Page 34
Section 8 — Exploded Views and Parts Lists Guardian Liquid-cooled 40 kW Generators Compartment - Drawing No. 0D8992 32 Generac ® Power Systems, Inc. BASE FRAME...
Page 35
SCREW HHC M8-1.25 X 16 G8.8 WASHER FLAT M6-1/4 ZINC WASHER LOCK M6-1/4 NUT HEX 1/4-20 STEEL GASKET DOOR RUBBER SCREW SHOULDER COVER EXHAUST HOLE FASTENER RATCHET STRIP SEALANT 1/8 X 1 WASHER FLAT 5/16 ZINC Generac ® Power Systems, Inc. 33...
Page 36
Section 8 — Exploded Views and Parts Lists (Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator Control Panel 4.3L – Drawing No. 0D4995-F 34 Generac ® Power Systems, Inc.
0D5324 REF. 0A9611 REF. 074908 0E3783 * PART OF CONTROL PANEL WIRE HARNESS Generac DESCRIPTION FREQUENCY METER 240V 55-65HZ DECAL EXERCISE INFO DECAL CUST CONN BOX ASSY L.C. ELECT GOV CAPACITOR FILTER ASY BLOCK TERM 20A 2 X 6 X 1100V...
Page 38
Section 8 — Exploded Views and Parts Lists (Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generator Control Panel – Drawing No. 0D6978-C 36 Generac ® Power Systems, Inc.
Page 39
0C2323 0A2284 0C1127 0D5324 0A9611 074908 0E3783 * PART OF CONTROL PANEL WIRE HARNESS Generac DESCRIPTION DECAL EXERCISE INFO DECAL CUST CONN BOX CONTROLLER, B-C #DPG-2103 CAPACITOR FILTER ASY BLOCK TERM 20A 2 X 6 X 1100V COVER PLATE AVR...
Page 40
Section 8 — Exploded Views and Parts Lists Guardian Liquid-cooled 40 kW Generators Connection Box – Drawing No. 0E6892-A 38 Generac ® Power Systems, Inc.
Page 41
COVER TERMINALS S (QJ 2P) WASHER LOCK 3/8 NUT HEX 3/8-16 STEEL SCREW SHC 1/4-20 X 4.5 G8.8 NZ SCREW SHC 3/8-16 X 3/4 G5 NEUTRAL BLOCK 390/200-400A JUNCTION BLOCK 3/8-16 SCREW PHTT M5-0.8 X 16 ZYC Generac ® Power Systems, Inc. 39...
Page 42
Section 8 — Exploded Views and Parts Lists Guardian Liquid-cooled 40 kW Generators Generator – Drawing No. 0E6891 40 Generac ® Power Systems, Inc.
Page 43
SHROUD ALTERNATOR SHEET METAL SCREEN SHROUD SAE BRACKET TENSIONER SAE SCROLL TRIM VINYL BLACK 1/8 GP WASHER LOCK M6-1/4 SCREW HHC M6-1.0 X 25 G8.8 SCREW HHC M6-1.0 X 16 G8.8 SCREW SWAGE 1/4-20 X 1/2 Z/YC Generac ® Power Systems, Inc. 41...
Page 44
Section 8 — Exploded Views and Parts Lists Guardian Liquid-cooled 40 kW Generators Engine – Drawing No. 0D6980-B 42 Generac ® Power Systems, Inc.
Page 46
Section 8 — Exploded Views and Parts Lists Guardian Liquid-cooled 40 kW Generators Engine – Drawing No. 0A4304-L 44 Generac ® Power Systems, Inc.
Page 47
WASHER FLAT HEAVY DUTY WASHER LOCK M10 SCREW HHC M10-1.5 X 25 G8.8 BOLT TENSIONER PULLEY NUT HEX M10-1.5 G8 YEL CHR SPARK PLUG 5.7L GM WASHER FLAT M12 CLAMP VINYL 1.06 X .406 Z FILTER OIL Generac ® Power Systems, Inc. 45...
Page 48
Section 8 — Exploded Views and Parts Lists Guardian Liquid-cooled 40 kW Generators 4.3L Radiator – Drawing No. 0D7992-D 46 Generac ® Power Systems, Inc.
Page 49
SCREW HHC 1/4-20 X 1 G5 WASHER LOCK M6-1/4 WASHER FLAT 1/4 ZINC SCREEN FRONT SCREW HHTT 1/4-20 X 1 CZ WASHER LOCK M6-1/4 WASHER FLAT 1/4 ZINC CAP RADIATOR 13 PSI-FOR SERVICE ONLY Generac ® Power Systems, Inc. 47...
Page 50
TUBE, CROSS OVER 0E0698 TUBE, 90 ELBOW 0C4170 BRACKET EXHAUST SHIELD 0C4305 SHIELD A-GRP HEAT 0C2454 SCREW TH-FRM M6-1 X 16 N WA Z/JS 48 Generac ® Power Systems, Inc. COMPARTMENT FRONT ITEM PART NO. QTY. DESCRIPTION 0C3433A CLAMP BAND 2.5"...
Page 51
4.3L Air Cleaner – Drawing No. 0E0712 DESCRIPTION NUT WING 1/4-20 NYLK PLATE AIR CLEANER TOP FILTER AIR 11.5" CA326 PLATE,AIR CLEANR BOT STUD TH 1/4-20 X 3 G2 ZNC FULL NUT HEX 1/4-20 STEEL GROMMET CONNECTOR C/C VENT Generac ® Power Systems, Inc. 49...
Page 52
Section 8 — Exploded Views and Parts Lists (Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generators 4.3L Nat. Gas Fuel System – Drawing No. 0E7011 50 Generac ® Power Systems, Inc.
Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the completion of all scheduled maintenance.
Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim. Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of such an unapproved, add-on, modified, counterfeit and/or “grey market”...
GUARDIAN “EMERGENCY AUTOMATIC STANDBY GENERATORS” For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below.