1.6

MAIN CIRCUIT BREAKER

The generator's main circuit breaker is included with the
unit as shipped from the factory. The breaker for each
unit is described as follows:
Model Number
0043736
0046265
1.7

ENGINE PROTECTIVE DEVICES

The engine has several safety switches that cause
it to automatically shut down under the following condi-
tions: low oil pressure, high coolant temperature, low
coolant level, engine overspeed and overcrank.
1.7.1
LOW OIL PRESSURE SWITCH
This switch is normally closed (N.C.) but is held open by
engine oil pressure during engine running. Should oper-
ating oil pressure drop below approximately 10 psi (68
kPa), the switch contacts close, and the engine shuts down
automatically (Figure 1.2).
Figure 1.2 – Engine Protective Devices
1.7.2
HIGH COOLANT TEMPERATURE SWITCH
This normally open (N.O.) thermostatic switch has a
sensing tip that is immersed in captive coolant. Should
the coolant temperature exceed approximately 121° C
(250° F), the switch contacts close, which causes the
engine to shut down automatically (Figure 1.2).
Circuit Breaker Rating
200-amp breaker
200-amp breaker
Section 1 — General Information
Guardian Liquid-cooled 40 kW Generator
1.7.3
LOW COOLANT LEVEL SWITCH
Should the engine coolant level drop below the level of the
high coolant temperature switch, it is possible for the
engine to overheat without automatic shut down. To pre-
vent such overheating without automatic shut down, the
engine has a low coolant level sensor. If the engine coolant
drops too low, the engine automatically shuts down
(Figure 1.2).
1.7.4
OVERSPEED SHUTDOWN
The control module assembly (CMA) circuit board on
liquid-cooled units receives AC frequency (rpm) signals
directly from the stator AC power windings. Should AC
frequency exceed approximately 72 Hertz, circuit board
action will automatically shut down the engine.
1.7.5
OVERCRANK SHUTDOWN
After 90 seconds of crank-rest cycles (about seven sec-
onds cranking/seven seconds at rest), this function ends
cranking if the engine fails to start in that 90-second
span.
1.7.6
DC FUSE
This fuse is located on the front panel of the control sys-
tem. It protects the panel wiring and components from
damaging overload. Always remove this fuse before
commencing work on the generator. The unit will not
start or crank if the fuse is blown. Replace the fuse with
one of the same size, type, and rating. Generac uses an
AGC fuse rated at 15 amps.
1.8

SPECIFICATIONS

1.8.1 GENERATOR
Models ..............................................0043736, 0046265
Rated Maximum Continuous
AC Power Output (kW)*..................................................40
Rated Voltage (volts) ................................................120/240
Rated Maximum Continuous
Current at 240 Volts, Single-phase (amps)................................167
Number of Rotor Poles ........................................................4
Driven Speed of Rotor (rpm) ........................................1,800
Type of Stator ........................................................Four-wire
Rotor Excitation System ..................................Direct Excited
Stator Insulation ....................................................Class "H"
Rotor Insulation ......................................................Class "F"
*Rated power of generator is subject to and limited by such factors as ambient tempera-
ture, altitude, engine condition and other factors. Engine power will decrease about 3.5
percent for each 1,000 feet above sea level; and also will decrease an additional 1 percent
for each 6° C (10° F) above 15.5° C (60° F) ambient. Maximum output power of the gener-
ator is limited by maximum engine power.