Electrical specifications
Power supply
Voltage range
Power consumption
Efficiency
Maximum no-load consumption
Mains power frequency
Battery
On-battery runtime
Charging time
Data acquisition
Resolution
Sampling frequency
Input signal frequency
Circuit types
THD
Averaging period
Demand interval
Data storage
Memory size
Logging period
Interfaces
USB-A
USB-mini
Extension port
Voltage inputs
Number of inputs
Maximum input voltage
Input impedance
Bandwidth (-3 dB)
Scaling
Measurement category
Current inputs
Number of inputs
Input voltage
Rogowski coil input
Range
Bandwidth (-3 dB)
Scaling
1
The number of possible logging sessions and logging period depends on user requirements.
4 Fluke Corporation
Fluke 1730 Three-Phase Electrical Energy Logger
Shop for Fluke products online at:
100 V to 500 V using safety plug input when powering from the measurement
circuit
100 V to 240 V using standard power cord (IEC 60320 C7)
Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
≥ 68.2 % (in accordance with energy efficiency regulations)
< 0.3 W only when powered using IEC 60320 input
50/60 Hz ± 15 %
Li-ion 3.7 V, 9.25 Wh, customer-replaceable
Four hours in standard operating mode, up to 5.5 hours in power saving mode
< 6 hours
16-bit synchronous sampling
5120 Hz
50/60 Hz (42.5 to 69 Hz)
1-ϕ, 1-ϕ IT, Split phase, 3-ϕ delta, 3-ϕ wye, 3-ϕ wye IT, 3-ϕ wye balanced, 3-ϕ
Aron/Blondel (2-element delta), 3-ϕ delta open leg, Currents only (load studies)
THD for voltage and current is calculated using 25 harmonics
User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
User selectable: 5 min, 10 min, 15 min, 20 min, 30 min
Internal flash memory (not user replaceable)
Typical 20 logging sessions of 10 weeks with 10-minute intervals
Averaging period
1 second
5 seconds
10 seconds
30 seconds
1 minute
5 minutes
10 minutes
15 minutes
30 minutes
File transfer via USB flash drive, firmware updates
Max. current: 120 mA
Data download device to PC
Accessories
4 (3 phases and neutral)
1000 V
, CF 1.7
rms
10 MΩ
2.5 kHz
1:1, 10:1, 100:1, 1000:1 and variable
1000 V CAT III/600 V CAT IV
3, mode selected automatically for attached sensor
Clamp input: 500 mV
/50 mV
rms
rms
150 mV
/15 mV
at 50 Hz, 180 mV
rms
rms
probe range
1 A to 150 A/10 A to 1500 A with thin iFlex flexible current probe, 12 inches
3 A to 300 A/30 A to 3000 A with thin Flex flexible current probe, 24 inches
6 A to 600 A/60 A to 6000 A with thin iFlex flexible current probe, 36 inches
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
1.5 kHz
1:1 and variable
MyFlukeStore
www.
Recommended
Logging Period
for 20 sessions
for 1 session
3 hours
15 hours
28 hours
3.5 days
10 weeks
7 days
20 weeks
5 weeks
10 weeks
> 2 years
3.5 months
> 2 years
7 months
> 2 years
; CF 2.8
/18 mV
at 60 Hz; CF 4; all at nominal
rms
rms
.com
1
2.5 days
12 days
24 days
2 years
1
1.877.766.5412

Advertisement

loading

This manual is also suitable for:

1730/us1730/eu1730/intl1730