Engine Shutdown
To shutdown the generator use the following procedure:
1. Place both the MAIN, GFCI and LOAD circuit breakers
to the "OFF position".
2. Let the engine cool by running it for 3-5 minutes with no
load applied.
3. Place the Off/Manual/Auto Switch (Figure 61) in the "OFF/
RESET" position.
Figure 61. Off/Manual Auto Switch (OFF)
4. Verify that the "Engine Running" status LED (Figure 62)
on the Microprocessor Engine Control Module (MPEC)
display is "OFF" (not lit).
Figure 62. MPEC Engine Running
Status LED (OFF)
5. Remove the load from the UVW terminal strip (Figure 16).
PAGE 54 — DCA-220SSK — PARTS AND OPERATION MANUAL (STD) — REV. #3 (06/05/01)
DCA-220SSK — GENERATOR SHUTDOWN PROCEDURE
Emergency Stop
1. To stop the engine in the event of an emergency, PUSH
the emergency stop button ( Figure 63) inward. This button
is located on the generator's engine operating panel,
see page 32, Figure 11.
Figure 63. Emergency Stop Button
CAUTION:
NEVER stop the engine suddenly except
in an emergency. DO NOT use the
emergency stop switch a as method of
shutting down the engine. This switch is
ONLY to be used in the event of an
emergency.