Output Terminal Panel - MULTIQUIP Power WHISPERWATT DCA-400SPK Parts And Operation Manual

Mq power whisperwatt generator
Table of Contents

Advertisement

480 Volt Set position
The voltage change-over board 480V set position uses all
6 plates in 3 different connection places. There are 2
plates at every position (Every plate is used). See figure
23 below.
FIGURE 23. Voltage Change-over Board 480V set position.
3 Phase, 480 Volt
The following connection, with the voltage change-over
board set into the 480V set position (See Figure 23), can
offer THREE PHASE power at 480V. After hooking up the
hard wires to the lugs as shown in figure 24 below, 480V
will be the voltage output.
FIGURE 24. Hard Wire Hookup for Three Phase 480V
DCA-400SPK — PARTS AND OPERATION MANUAL — REV. #0 (06/19/01) — PAGE 39
DCA-400SPK — OUTPUT TERMINAL PANEL OVERVIEW
Single Phase, 480 Volt
The following connection, with the voltage change-over
board set into the 480V set position (See Figure 23), can
offer SINGLE PHASE power at 480V. After hooking up
the hard wires to the lugs as shown in figure 25 below,
480V will be the voltage output.
FIGURE 25. Hard Wire Hookup for Single Phase 480V
Single Phase, 277 Volt
The following connection, with the voltage change-over
board set into the 480V set position (See Figure 23), can
offer SINGLE PHASE power at 277V. After hooking up
the hard wires to the lugs as shown in figure 26 below,
277V will be the voltage output.
FIGURE 26. Hard Wire Hookup for Single Phase 277V