Vertical (Through-The-Roof) Installations - Montigo MD34-DV-2 Installation & Operation Manual

Homefire plus modular gas fireplace
Hide thumbs Also See for MD34-DV-2:
Table of Contents

Advertisement

MD34-DV-2 Homefire
B. Vertical (Through-The-Roof) Installations
n
n
n
A - Termination
B - Flex sections
C - Solid sections
D - Support Ring & Plate
E - Firestop
F - Roof Flashing
Storm collar
Roof flashing
30' max.
30' max.
MEXT
MXT-10
Adaptor
Flue
Collar
* Minimum 1" clearance to all combustibles
Figure 13.
Page 8
Installation
MVTK-1
MFL-1 (12" section)
MFL-2 (24" section)
MFL-3 (36" section)
MFL-4 (48" section)
MEXT-1 (12" section)
MEXT-2 (24" section)
MEXT-3 (36" section)
MEXT-4 (48" section)
MSPXT-8 (7" dia.)
FS-7 (7" dia.)
MRF-7 (1/12 - 7/12 pitch)
MRF-12 (7/12 - 12/12 pt.)
MRF-16 (12/12 - 16/12 pt.)
2' min.
MEXT
Solid Section
Firestop
Support ring
Support plate
Firestop
Top Vent
n
(each offset has two 90° bends)
Storm collar
Roof flashing
30' max.
30' max.
* Minimum 1" clearance to all combustibles
Figure 14a.
Storm collar
Roof flashing
30' max.
30' max.
* Minimum 1" clearance to all combustibles
Figure 14b.
2' min.
Support ring
Support plate
Firestop
2' min.
Support straps or
support plate & ring
Firestop
Support plate
& ring
Firestop
2'
Firestop