Connecting Ethernet Media; Description; Connecting St-Type Fiber Optics (Twist-Lock); Connecting Sc-Type Fiber Optics (Snap-In) - GE MultiLink ML1600 Instruction Manual

Ethernet communications switch
Hide thumbs Also See for MultiLink ML1600:
Table of Contents

Advertisement

CONNECTING ETHERNET MEDIA

3.2
Connecting Ethernet Media
3.2.1

Description

3.2.2

Connecting ST-type Fiber Optics (twist-lock)

Note
3.2.3

Connecting SC-type Fiber Optics (snap-in)

3–2
The ML1600 switches are specifically designed to support standard Ethernet media types
within a single unit. This is accomplished by using a family of modules that are individually
selected and configured. Refer to Communications Modules on page 2–3 for details on
these modules.
The supported media types with the corresponding IEEE 802.3, 802.3D, 802.3u, 802.3AB
and 802.3z standards and connector types are as follows:
Table 3–1: Ethernet media
IEEE standard
Media type
100Base-FX
multi-mode fiber
single-mode fiber 5 km
10Base-T
twisted-pair
100Base-TX
100Base-FX
The following procedure applies to installations using modules with ST-type fiber
connectors. These are type A1, A2, A4, A5, A6, and A7 modules.
1.
Before connecting the fiber optic cable, remove the protective dust caps from
the tips of the connectors on the module. Save these dust caps for future use.
2.
Wipe clean the ends of the dual connectors with a soft cloth or lint-free lens
tissue dampened in alcohol. Ensure the connectors are clean before
proceeding.
One strand of the duplex fiber optic cable is coded using color bands at regular intervals.
The color-coded strand must be used on the associated ports at each end of the fiber optic
segment.
3.
Connect the transmit (TX) port on the module (light colored post) to the receive
(RX) port of the remote device. Begin with the color-coded strand of the cable
for this first TX-to-RX connection.
4.
Connect the receive (RX) port on the module (dark colored post) to the transmit
(TX) port of the remote device. Use the non-color coded fiber strand.
5.
The LINK LED on the module will illuminate when a connection has been
established at both ends (assuming power is ON). If LINK is not lit after cable
connection, the cause may be improper cable polarity. Swap the fiber cables
at the module connector to remedy this situation.
The following procedure applies to installations using modules with SC-type fiber
connectors. These include the A3, A8, A9, G3, G4, and G5 modules.
MULTILINK ML1600 ETHERNET COMMUNICATIONS SWITCH – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
Distance
220 m
100 m
100 m