The Zone Controller; Specifications - Bosch DDC KIT Installation And Operation Manual

Table of Contents

Advertisement

4
DDC KIT

The ZOne COnTrOller

The Digital Direct Control board also known as DDC
and shown in Figure #1 is used in most configure to
order applications.
It is BACnet® native which makes it flexible and easy
to integrate into existing Building Automation
Systems (BAS). The controller provides the end user
with a superior amount of information when
compared to a traditional thermostat.
The controller is programmed in the factory with
software versions that suit the different application
for the models offered by Bosch. User settings such
as the time and schedules can be preprogrammed or
also change during the installation of the product.
figure #1 - Zone Controller

speCIfICaTIOns

power: 24VAC ± 10%, 50-60Hz, 20VA power
consumption (Single Class II 70VA or 100VA option
available)
physical: Rugged plastic housing protects circuitry.
environmental Operating range: 40° to 130°F (-17.8°
to 54.4°C); 10 to 90% relative humidity, non-
condensing
8 733 900 571
Digital Outputs: Five digital outputs relay contacts
rated at 1A resistive @ 24VAC; configured as dry
contact, normally open.
Universal Inputs: 8 inputs. Inputs 1 and 2 are
configurable for 0-5VDC, 10K ohm thermistor, or
dry contact; inputs 3 and 4 support thermistor or
dry contact only; inputs 5 and 6 support
thermistor, dry contact, or LogiStat.
standard Communication ports:
Comm port: 3-pin port configurable for ARC156
(BACnet-over- ARC156) or EIA-
485communications (BACnet MS/TP, Modbus
RTU, orN2).
rnet port: 4-pin port for interface with remote
mounted BACview6 or RS sensors
local access port: For local communication with a
laptop computer running WebCTRL or for
communication with a BACview6.
status Indication: Visual (LED) status of network
communication, running, errors, power, and all
digital outputs
battery: Lithium 3V coin cell battery, CR2032, provides
a minimum of 10,000 hours of Data retention
during power outages
protection: Surge and transient protection circuitry for
power and communications.
listed by: FCC Part 15 - Subpart B - Class A. Pending
listings at the time of publishing this document: UL
916 (PAZX), cUL C22.2 No. 205-M1983 (PAZX7),
CE (1997).
Weight: 0.6 lbs. (0.27 Kg).
Overall Dimensions: 5-1/16" (width) by 5-11/16"
(height) by 1-1/2" (recommended panel depth).
129mm (width) by 144mm (height) by 38mm
(recommended panel depth).
Mounting hole Dimensions: Two mounting holes
center line as at left with 5-9/16" (141mm)
Spacing (height)
Subject to change without prior notice