menus. The About screen is still accessible. Once
a valid code has been entered on the Daikin
ENVi thermostat, access to restricted features
will be allowed until the Daikin ENVi thermostat
backlight timer has expired.
Temperature Range
You can configure the Daikin ENVi thermostat so
only a specific heat and/or cool set point range
is permitted.
Heat Temp Range
maximum or minimum heat set points then
press OK. Users will not be able to set the
Daikin ENVi thermostat to a temperature
above this limit.
Heat Min Temp: 45 to 68 °F (7 to 20 °C)
Heat Max Temp: 57 to 80 °F (14 to 26.5 °C)
Cool Temp Range
the maximum and minimum cool set
points and then press OK. Users will not be
able to set the Daikin ENVi thermostat to a
temperature below this limit.
Cool Min Temp: 65 to 83 °F (18.5 to 28.5 °C)
Cool Max Temp: 77 to 95 °F (25 to 35 °C)
Intelligent Eye
Some models of the Indoor Unit include an
intelligent eye, an infrared sensor that detects
room occupancy. It adjust the set point by 3.6°F
(2°C) if no movement is detected in order to
save energy (+3.6°F/+2°C if cooling, –3.6°F/–2°C
if heating).
To use intelligent eye, you must enable this
option in the Daikin ENVi thermostat and
Press
▲
or ▼ select the
Press
▲
or ▼ to select