Configuration And Wiring - Bosch MIYN46 User Manual

Wall transmitter
Table of Contents

Advertisement

14
en | Installation
4.2.8

Configuration and Wiring

CR 2450
battery
Reset
Connector J4:
External Call for Help
trigger (pear push button)
(o)
Solder bridges B1 and B2 are located on the bottom side of the PCB:
NC-B2-NO
Fig. 4.2 Configuration and Wiring
NOTICE!
i
Setting up one or more inputs to "NC" position results to higher power consumption. This con-
figuration should be used with external power supply or will reduce the battery life.
970.035b | F.01U.278.521 | v2.0 | 2012.12
N
NC
N
NC
J5
1 2 3 4 5 6
N
NC
J4
5
4
3
2
1
NC-B1-NO
Solder Bridges (if soldered):
B8 Call for Assistance only by
B7
Call for Assistance from terminals J6[4-5]
B6 No
Staff Presence
B5 No Daily Message
B4 Not used
B3 Not used
(o)
B1 REL 1 Call for Help
(o)
B2 REL 2 Staff Presence
Terminal J5
1 External 12-24 VDC power supply
2 GND (0 V)
3-4 REL 1 Call for Help
5-6 REL 2 Staff Presence
Connector J7:
Presence / Staff identification (optional)
Terminal J6:
4-5 Reserve Call or Call for Assistance
3-4 Technical Alarm
1-2 Call for Help
J6
J1 External Call for Help trigger
input polarity
J2 Polarity of Technical Alarm input
J3 Polarity of
User Manual US
MIYN46 Wall Transmitter
Staff Presence
processing
polarity
polarity
terminal J6[4-5]
input
Bosch Security Systems