3-10. Electrical Service Requirements For 750 Ampere Models*
Input Voltage
Input Amperes At Rated Output
Circuit Breaker Size In Amperes
1
Fuse Size In Amperes
Input Conductor Size In AWG/Kcmil
Maximum Input Conductor Length In Feet (Meters)
Grounding Conductor Size In AWG/Kcmil
*
These values are calculated from the 1996 edition of the National Electrical Code (NEC).
1 Standard fuse or circuit breaker size is that closest to 150% of rated input amperage of the welding power source (Article 630-12(a) of NEC).
2 Input conductor size is for insulated copper wire with 75 C rating with not more than three single current-carrying conductors in a cable or raceway
(Table 310-16 of NEC).
3 Maximum length is to prevent more than a 3% voltage drop between service entrance and input terminals of the welding power source (Articles
210-19(a) and 215-2(b) of NEC).
4 The grounding conductor shall be colored or identified as specified in the NEC. Grounding conductor size for copper wire is not required to be larger