Displaying the Frequency, Power, and Current Data

Select Meters on the Main Menu to view the frequency, power and current of either the main
module or any of the other electronics modules.
This submenu provides information on virtual meters monitoring the UPS voltages. Scroll up
and down through the menu using the Center button. If the words continue off the screen,
scroll right and left to read the message. Press the Enter button to view selections. Table 3-5
lists the options under the Meters menu.
Table 3-5: Main Module and Electronics Modules M1-M4 Meter Options
Input Frequency
Output Frequency
HP Uninterruptible Power System R12000 XR Models User Guide
Main Menu
Meters
LCD Display
Explanation
Input Volts
The utility voltage
Output Volts
The voltage available at the UPS output receptacles
The utility frequency in Hertz
The frequency in Hertz available at the UPS output
receptacles
Output Power
The output power is shown in a bar graph. This example
shows 120% load (overload). There are ten squares in
MM or Mx
front of the 100% line. Each represents a 10% load. The
two squares past the line each represent 10% of overload
(20% overload in all).
Output Power
In contrast, this display shows a 60% load.
----│-- MM or Mx
Battery Volts
The battery voltage
Input Current
The input current