Horizontal Vent Tables And Figures - Lennox MPD-3530CNM-B Installation Instructions Manual

Merit plus series mpd direct-vent gas fireplaces
Table of Contents

Advertisement

LENNOX HEARTH PRODUCTS • MERIT
HORIZONTAL VENT FIGURES/TABLES
Note: Secure Vent components (rigid vent pipe and terminal) are
shown in the figures; Secure Flex components (flexible vent pipe and
terminal) may also be used.
Note: Two 45 degree elbows may be used in place of one 90 degree
elbow. The same rise to run ratios, as shown in the venting figures for
90 elbows, must be followed if 45 degree elbows are used.
Note: It is very important that the horizontal/inclined run be maintained
in a straight (no dips) and recommended to be in a slightly elevated
plane, in a direction away from the fireplace of 1/4" rise per foot (20
mm per meter) which is ideal, though rise per foot run ratios that are
smaller are acceptable all the way down to at or near level.
Note: SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must
be used anytime vent pipe passes through a combustible floor or ceiling.
SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be
used anytime vent pipe passes through a combustible wall.
WARNING
Under no circumstances, may separate sections of
concentric flexible vent pipe be joined together.
Venting Components Required for Various Exterior Wall Thick-
nesses, when using Typical Termination Kits
Vent Components Required
Termination Kit Only
Termination Kit and 6 In. Vent
Section (SV4.5L6)
Termination Kit and 12 in.
Vent Section (SV4.5L12)
Termination Kit and Tele-
scopic Section (SV4.5L12)
Note: See Figure 37 showing wall thickness range
Table 8
when using SV4.5HT-2 termination kit.
H = 28 in. (711 mm) Maximum.
Wall Firestop/
Spacer
SV4.5HF**
7 in
(178 mm)
Only the square termination (SV4.5HT-2) may be used.
See Table 8 as an aid in venting component selection
for a particular range of exterior wall thicknesses.
Figure 38: Rear Vent - NO ELBOWS
PLUS DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
®
Exterior Wall Thickness - inches (mm)
6 to 9-1/4 (152 to 235)
10-3/4 to 14 (273 to 356)
16-3/4 to 20 (426 to 508)
11-3/4 to 20 (299 to 508)
H
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
TABLE F
H Maximum
V Minimum
(meters)
(meters)
feet
feet
(0.914)
Elbow Only
3
**When using Secure
Flex, use Wall Firestop/
Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
See Table 3 as an aid in venting component selection
for a particular range of exterior wall thicknesses.
Figure 39: Top Vent - ONE 90-DEGREE ELBOW -
ELBOW CONNECTION AT APPLIANCE
TABLE G
H Maximum
V Minimum
(meters)
(meters)
feet
feet
5
(1.524)
1
(0.305)
10
(3.048)
2
(0.610)
15
(4.572)
3
(0.914)
20
(6.096)
4
(1.219)
V + H = 40 feet (12.2 m) Max.
H = 20 ft. (6.096 m) Max.
H
Wall Firestop/
Spacer SV4.5HF**
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
See Table 8 as an aid in venting component selection
for a particular range of exterior wall thicknesses.
Figure 40: Top Vent - ONE 90-DEGREE ELBOW -
ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
H
Wall Firestop/
Spacer
SV4.5HF**
Example: If 20 feet of (H)
horizontal vent run is needed,
then 4 feet minimum of (V)
vertical vent will be required.
This table shows a 1 (V) to 5
(H) ratio. For every 1 foot of
(V) vertical, you are allowed
5 feet of (H) horizontal run,
up to a maximum horizontal
run of 20 feet.
V
Ceiling
Firestop/
Spacer
SV4.5VF*
V
21

Advertisement

Table of Contents
loading

Table of Contents