Horizontal Vent Tables And Figures - Lennox MPDT33RNM Installation Instructions Manual

Merit plus series mpd direct-vent gas fireplaces
Table of Contents

Advertisement

LENNOX HEARTH PRODUCTS • MERIT PLUS
HORIZONTAL VENT FIGURES/TABLES
Note: Secure Vent
components (rigid vent pipe and terminal) are
®
shown in the figures; Secure Flex
terminal) may also be used.
Note: Two 45 degree elbows may be used in place of one 90 degree
elbow. The same rise to run ratios, as shown in the venting figures for
90 elbows, must be followed if 45 degree elbows are used.
Note: It is very important that the horizontal/inclined run be
maintained in a straight (no dips), slightly elevated plane. The
recommended incline is approximately 1/4 in. per foot (20 mm per
meter) horizontal, in a direction away from the fireplace. The rise
per foot run ratios that are smaller are acceptable all the way down to
at or near level.
Note: SV4.5VF (Secure Vent
), SF4.5VF (Secure Flex) firestop/spacer
®
must be used anytime vent pipe passes through a combustible floor or
ceiling. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer
must be used anytime vent pipe passes through a combustible wall.
WARNING
Under no circumstances, may separate sections of
concentric flexible vent pipe be joined together.
Venting Components Required for Various Exterior Wall Thick-
nesses, when using Typical Termination Kits
Vent Components Required
Termination Kit Only
Termination Kit and 6 in.
Vent Section (SV4.5L6)
Termination Kit and 12 in.
Vent Section (SV4.5L12)
Termination Kit and
Telescopic Section
(SV4.5L12)
Note: See Figure 34 showing wall thickness range
Table 9
when using SV4.5HT-2 termination kit.
H = 28 in. (711 mm) Maximum.
Wall Firestop/
Spacer
SV4.5HF**
7 in
(178 mm)
Only the square termination (SV4.5HT-2) may be used.
See Table 9 as an aid in venting component selection for a particular
range of exterior wall thicknesses.
Figure 35: Rear Vent—NO ELBOWS
DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
®
components (flexible vent pipe and
®
Exterior Wall Thickness—in. (mm)
6–9 1/4 (152–235)
10 3/4–14 (2733–356)
16 3/4–20 (426–508)
11 3/4–20 (299–508)
H
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
TABLE F
H Maximum
V Minimum
feet
(meters)
(meters)
feet
(0.914)
Elbow Only
3
**When using Secure
Flex, use Wall Firestop/
Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
See Table 9 as an aid in venting component selection for a particular range of
exterior wall thicknesses.
Figure 36: Top Vent—ONE 90-DEGREE ELBOW—
ELBOW CONNECTION AT APPLIANCE
TABLE G
H Maximum
V Minimum
(meters)
(meters)
feet
feet
5
(1.524)
1
(0.305)
10
(3.048)
2
(0.610)
15
(4.572)
3
(0.914)
20
(6.096)
4
(1.219)
V + H = 40 feet (12.2 m) Max.
H = 20 ft. (6.096 m) Max.
H
Wall Firestop/
Spacer SV4.5HF**
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Square termination (SV4.5HT-2) shown.
See Table 9 as an aid in venting component selection for a particular range
of exterior wall thicknesses.
Note: Install the U-shaped vent restrictor in any vent run with more
than 8 ft of vertical rise (See Page 13).
Figure 37: Top Vent—ONE 90-DEGREE ELBOW—
ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE
Note: Install the U-shaped vent
restrictor in any vent run with
more than 8 ft of vertical rise
(See Page 13).
H
Wall Firestop/
Spacer
SV4.5HF**
Example: If 20 feet of (H)
horizontal vent run is needed,
then 4 feet minimum of (V)
vertical vent will be required.
This table shows a 1 (V) to 5
(H) ratio. For every 1 foot of
(V) vertical, you are allowed 5
feet of (H) horizontal run, up
to a maximum horizontal run
of 20 feet.
V
Ceiling
Firestop/
Spacer
SV4.5VF*
V
21

Advertisement

Table of Contents
loading

Table of Contents