Condensate Drainage; Water System - Keston K130 Installation And Servicing Instructions

Fan powered high efficiency condensing gas boiler
Table of Contents

Advertisement

WD52/0/1997
c.
Always thoroughly deburr all pipes and, most important, remove shavings from
within the pipe.
d.
e.
f.
g.
h.
3.5

CONDENSATE DRAINAGE

Connect the condensate drainage system to the boiler. It is advisable to use a detachable
fitting at connection to the boiler to enable easy removal for servicing.
Fill the condensate trap by pouring water into the boiler flue spigot until water is seen to
flow freely from the condensate drainage system. Make the final connection of flue pipe to
the boiler.
Details are provided in Chapter 2 - Section 2.11 Condensate Drainage
Connection :
3.6

WATER SYSTEM

Connect the flow and return pipework to the boiler. Ensure a detachable coupling is used
at connection to the boiler (ie compression fitting) to enable heat exchanger removal if
required. Details of system requirements are given in Chapter 2 - Section 2.7 Water
Systems.
Installation & Servicing Instructions
Chapter 3 : Installation
Measure, cut and check the air and flue pipes to pass to the exit from the
wall(s) or ceiling.
Assemble, using adhesive, the pipework from the boiler connections to
the exit from the first wall/ceiling (remount the boiler if removed). When
pushing pipe through walls, ensure grit and dust is not allowed to enter
the pipe.
Ensure pipes are fully engaged into sockets.
Connect the condensate drainage system and fill the condensate trap by
pouring water down the boiler flue spigot ( See Section 3.5 Condensate
Drainage).
Make the final connection of flue and air pipe to the boiler using
push on, or plastic compression
couplings. Ensure that the connectors
are set vertically otherwise leakage of
condensate may occur which will
corrode the casing. Do not use
adhesive on the 'push on' end of
connecting couplings.
Using the same methods drill any
further holes (always covering existing
pipework), cut and assemble the
pipework.
From outside, complete the two terminations - See Section 2.8 Flue
System and make good all holes.
Support any pipes whose route could be displaced either of its own
accord or by accident. Any horizontal run over 1m or vertical runs of any
length must always be supported. Brackets should be placed at intervals
of approximately 1m.
Check all connections for security and re-seal any joints using sovent
cement where soundness may be in doubt.
Note:
It is equally important to seal the air inlet with solvent cement as
the flue outlet pipe joints.
22 mm plastic pipe.
The Keston 130 Condensing Boiler
Fully Engaged
Adhesive
F
A
Page : 18

Advertisement

Table of Contents
loading

Table of Contents