Keston 50 - GC Installation And Servicing Instructions page 50

Fan powered high efficiency condensing gas boiler
Table of Contents

Advertisement

WD50/2/1997
Chapter 7 : Replacement Of Parts
7.4.10 Gas Low Pressure Switch (Fig. 5.7.3 item 105)
7.5
GAS ORIFICE (Fig 5.7.3 item 91)
i)
ii)
iii)
iv)
v)
vi)
vii)
viii)
7.6
SPARK IGNITION/FLAME DETECTION ELECTRODE (Fig. 5.7.2 item 51)
i)
ii)
iii)
iv)
v)
vi)
7.7
BURNER HEAD & BURNER (Fig. 5.7.2 items 46 & 48)
i)
ii)
iii)
iv)
v)
vi)
vii)
viii)
ix)
x)
Installation & Servicing Instructions
i)
Isolate the appliance (Section 7.1)
ii)
Gain access (Section 7.2)
iii)
Remove the push on connectors to the gas low pressure switch taking
note of the correct positions.
iv)
Unscrew the gas low pressure switch from the brass holder.
v)
Reassemble (Section 7.3)
Isolate the appliance (Section 7.1)
Gain access (Section 7.2)
Unscrew and remove the brass plug from the gas outlet block.
Remove the rubber seal from the injector housing.
Insert a flat blade screwdriver into the exposed hole and unscrew the gas injector.
Check the injector is the correct size for the boiler size and fuel type.
Reassemble (Section 7.3)
NB :
When fitting the new gas injector ensure that the injector is screwed fully
home past the gas port into the chamber from the gas valve.
Reset the gas pressure (See Section 4 - Commissioning)
Isolate the appliance (Section 7.1)
Gain access (Section 7.2)
Remove the pull off HT lead to the spark ignition electrode.
Remove the burner head (Section 7.7 steps iv) to vii).
Undo the screws to the spark ignition electrode flange located on the burner
head and withdraw the spark ignition electrode.
Reassemble (Section 7.3)
NB:
When reassembling inspect the gasket for damage and replace if
necessary. With the new spark ignition electrode in place it is essential to
ensure the gap between the tip of the electrode and the burner surface is
4 mm. Distance above or below 4 mm will affect the ignition performance.
If necessary gently bend the electrode taking care not to damage the
ceramic insulator.
Isolate the appliance (Section 7.1)
Gain access (Section 7.2)
Remove the pull off HT lead to the spark ignition/flame detection electrode head.
Remove the four screws retaining the access panel (Fig. 5.7.4 item 6) and
remove the access panel from the top of the cabinet.
Remove the two allen screws fixing the flange gas/air mixture pipe connection to
the burner head.
Remove the four allen screws fixing the burner head to the top of the heat
exchanger.
Withdraw the burner & burner head from the top of the heat exchanger through
the access panel opening in the top of the cabinet.
Unscrew the burner from the burner head taking care not to damage the burner
mesh.
Reassemble (Section 7.3)
NB:
When reassembling inspect any gaskets for damage and replace if
necessary. Set the spark gas as detailed in Section 7.6.
Reset the gas rate (see Section 4 - Commissioning)
Page : 47
The Keston 50, 60 & 80 Condensing Boilers