Important initial information for the Technician

1.1

Safety

The boiler and related accessories reflect the state of the art and meet all applicable safety regulations.
1.2

Please note!

Your boiler and all accessories operate using 230 VAC electrical current. Improper installation or repair can pose
the danger of life-threatening electrical shock. (Building reg Part P .)
Caution symbols
Please take careful note of the following symbols in these Installation instructions.
Ignoring the identified warnings can lead to personal injury.
Ignoring the identified warnings can lead to malfunction of, or damage to the boiler or heating sys-
tem.
The specified safety requirements are to be followed in accordance with nationally applicable regula-
tions, standards and guidelines.
1.3

Fuel

The boilers are designed to burn the following fuels:
Pellets according to ÖNORM M7135 or DIN plus.
Significant criteria based on the standards are as follows:
Diameter 6 mm
Smooth surface
Residual moisture content max. 10%
Ash content max. 0.5%
Chemical/synthetic binding agents are strictly prohibited No impurities from varnish or paint residues, etc.
Length 80% between 15 – 30 mm
Density at least 1.1 kg/dm3
Energy content min. 18 MJ/kg = 5 kWh/kg
(in water-free condition)
Abraded particles max. 2.3%