System Power Requirements - NEC Express5800 1080Xd User Manual

Hide thumbs Also See for Express5800 1080Xd:
Table of Contents

Advertisement

System Power Requirements

Table 5 shows the electrical specifications for all Express5800/1000 Series server
configurations. Make sure your site meets these specifications.
Express5800/
System
1320Xd Main Cabinet
1160Xd Main Cabinet
1320Xd/1160Xd
Expansion Cabinet
1080Xd Cabinet
* See Power Dissipation Equation information in Table 6 to compute the power dissipation for your
configuration.
Express5800/
System
1320Xd Main Cabinet
1160Xd Main Cabinet
1080Xd Cabinet
Table 5. Server Cabinets Power Requirements
Power Requirement
200-240VAC
/50~60Hz/single phase
200-240VAC
/50~60Hz/single phase
200-240VAC
/50~60Hz/single phase
200-240VAC
/50~60Hz/single phase
Table 6. Power Dissipation Equations:
Power Dissipation (kVA) Equation
Power Dissipation (kVA) =
(Number of CPUs x 0.191) + (Number of PCI Units x 0.886) + 2.818
Power Dissipation (kVA) =
(Number of CPUs x 0.191) + (Number of PCI Units x 0.886)+ 1.409
Power Dissipation (kVA) =
(Number of CPUs x 0.22) + (Number of PCI Units x 0.886) + 1.71
Express5800/1080Xd/1160Xd/1320Xd Site Preparation Guide 11
Necessary
Power
Power
Dissipation
Capacity (A)
(kVA)*
22.1 min
5.3 min
44.6 max
10.7 max
16.3 min
3.9 min
27.1 max
6.5 max
3.8 min
.9 min
22.5 max
5.4 max
14.6 min
3.5 min
18.4 max
4.4 max
Power Drop
L6-30R 30A
4 required
L6-30R 30A
2 required
L6-30R 30A
4 required
L6-30R 30A
1 (hardwired)