*Units are rated with 25 ft (7.6 m) of lineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
Note: See unit Installation Instruction for proper installation.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
Acceptable vapor line diameters provide adequate oil return to the compressor while avoiding excessive capacity loss. The suction line
diameters shown in the chart below are acceptable for HP systems with Puron refrigerant:
Vapor Line Sizing and Cooling Capacity Losses - - Puronr Refrigerant 1- - Stage Heat Pump Applications
Maximum
Unit
Vapor Line
Liquid Line
Nominal
Diameters
Diameters
Size (Btuh)
(In.) OD
(In. OD)
18,000
1/2
1--- Stage
3/8
HP with
5/8
Puron
24,000
5/8
1--- Stage
3/8
HP with
3/4
Puron
30,000
5/8
1--- Stage
3/4
3/8
HP with
7/8
Puron
36,000
5/8
1--- Stage
3/8
3/4
HP with
7/8
Puron
42,000
3/4
1--- Stage
3/8
HP with
7/8
Puron
48,000
3/4
1--- Stage
3/8
HP with
7/8
Puron
60,000
3/4
1--- Stage
7/8
3/8
HP with
1 ---1/8
Puron
Standard Length = 80 ft. (24.4 m) or less total equivalent length
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Applica-