Specifications
Fluke 376
AC current via jaw
AC current via iFlex
™
DC current
AC voltage
DC voltage
Resistance
Frequency
Capacitance
True-rms
Continuity
Hold
Backlight
Min/Max/Avg
Inrush
Low pass filter
18 in iFlex Flexible
™
Current Probe
10 in iFlex Flexible
™
Current Probe
Wire capacity
Safety rating
Models
Feature Changes
Old model: Fluke 337
New model: Fluke 376
Includes all 337 features plus:
•
CAT IV 600 V, CAT III 1000 V
•
iFlex
•
1000 V ac/dc
Old model: Fluke 336
New model: Fluke 375
Includes all 336 features plus:
•
CAT IV 600 V, CAT III 1000 V
•
Optional iFlex
•
mV dc
New model: Fluke 374
Includes all 336 features
(except low pass filter) plus:
•
CAT IV 600 V, CAT III 1000 V
Old model: Fluke 335
New model: Fluke 374
Includes all 335 features plus:
•
CAT IV 600 V, CAT III 1000 V
•
Optional iFlex
New model: Fluke 373
Includes all 335 features
(except inrush) plus:
Old model: Fluke 334
New model: Fluke 374
Includes all 334 features plus:
•
CAT IV 600 V, CAT III 1000 V
•
Optional iFlex
•
True-rms
New model: Fluke 373
Includes all 334 features
(except inrush) plus:
•
CAT IV 300 V, CAT III 600 V
Old model: Fluke 333
New model: Fluke 373
Includes all 333 features plus:
•
CAT IV 300 V, CAT III 600 V
•
True-rms
2 Fluke Corporation 376 True-rms AC/DC Clamp Meter with iFlex
• Large, easy to read, backlight
display automatically sets the
correct measurement range
so you do not need to change
switch positions while taking
a measurement
• Three-year warranty
• Soft carrying case
Range
Resolution
999.9 A
0.1 A
2500 A
0.1 A
999.9 A
0.1 A
1000 V
0.1 V
1000 V
0.1 mV
60,000 Ω
0.1 Ω
500 Hz
0.1 Hz
1000 µF
1 µF
•
•
•
•
•
•
•
Included
Accessory
750 MCM or 2-500 MCM
CAT III 1000 V, CAT IV 600 V
•
mV dc
•
60 kΩ
•
2500 A ac
1000 µF
™
•
60 kΩ
•
1000 µF
•
2500 A ac
Min/Max/Avg
™
•
Optional iFlex
•
1000 µF
•
Min/Max/Avg
•
600 A ac/dc
•
1000 µF
•
2500 A ac
Min/Max/Avg
™
•
CAT IV 300 V, CAT III 600 V
•
1000 µF
•
600 A ac/dc
•
1000 µF
•
2500 A ac
Min/Max/Avg
™
•
True-rms
•
1000 µF
•
600 A ac
•
6000 Ω
•
1000 µF
™
Accuracy
2 % ± 5 digits
3 % ± 5 digits
2 % ± 5 digits
1.5 % ± 5 digits
1 % ± 5 digits
1 % ± 5 digits
0.5 % ± 5 digits
1 % ± 4 digits
2500 A ac
™
Ordering information
376 True-rms AC/DC Clamp
Meter with iFlex
™
Included
Clamp meter, 18-inch iFlex
probe, test leads, soft case,