Pushing the START-button will display the value of R
In this particular mode the values of RH and RS have no meaning.

Settings on the Tester

Refer to the Operation section in the Testers instruction manual.
The rotary switch of the tester must be in the R
- U
Set Test Voltage to 48 V (standard value)
m
- R
Set compensation resistance to 0,000 Ohms
k
- I
Set transformer ratio to 1000 (standard value)
- R*
Set to OFF (no meaning in this mode).
Stakeless Earth/Ground Resistance Testing
Erder
>10 cm
Note
Principle of Operation
.
E
3 pole position.
E
edw064.eps
69