3-Pole/4-Pole Measurement Of Single Earth Electrode Resistances - Fluke 1625 User Manual

Earth/ground tester
Hide thumbs Also See for 1625:
Table of Contents

Advertisement

Errors of the current transformer can be corrected as described in "Correcting
Clip-on Transformer Error".
3-pole/4-pole Measurement of Single Earth Electrode Re-
sistances
See Figure 12.
1625
EARTH / GROUND TESTER
START
H/C2
TEST
DISPLAY
S/P2
MENU
AC
Resistance
Earth/Ground Resistance 300 k
300 k
DC Low Resistance 3k
RA
R
R
2
POLE
4
POLE
3
2
POLE
POLE
4
POLE
4
POLE
CHANGE
ES/P1
ITEM
3
POLE
OFF
SELECT
E /C1
Figure 12. 3-pole/4-pole Measurement of Single Earth Electrode Resis-
Turn central rotary switch to position "A RE 3pole" or "A RE 4pole".
The instrument is to be wired according to picture and notices given on the
display.
A flashing of the sockets symbols EFGH or A, points to an incorrect
or incomplete connection of the measuring lead.
Fix clip-on transformer around the earth electrode to be measured.
Make sure that the clip-on transformation ratio set on the instrument corre-
sponds to the clip-on transformer used. Change settings if necessary (see
"Changing of all Data Settings with Personalised CODE")
4 Pole
Earth
electrode
tances
Earth/Ground Tester
Procedure of Measurements
Probe
>20 m
Auxiliary
earth
electrode
>20 m
edw015.eps
37