Zndc-Related Panel Events; Classic 2000 Mk Ii; Sigma Mk Ii - Zeta ZNDC Installation And Operating Manual

Networked digital communicator
Table of Contents

Advertisement

Zeta Alarm Systems.
Symptoms
7
This message shows up at the
panel: "Report Failure."
6 . 2
Z N D C - R e l a t e d P a n e l E v e n t s
C l a s s i c 2 0 0 0 M k I I
6 . 2 . 1
Type
Trouble
ZNDC Trouble
Trouble
ZNDC Phone Line #1 Fault
Trouble
ZNDC Phone Line #2 Fault
Trouble
ZNDC Phone Line #1 Report Failure
Trouble
ZNDC Phone Line #2 Report Failure
Trouble
ZNDC EEPROM Corrupt
Data Set To Defaults
Status
ZNDC Trouble Restored
Status
ZNDC Phone Line #1 Fault Restored
Status
ZNDC Phone Line #2 Fault Restored
6 . 2 . 2 S i g m a M k I I
Code
Event Text
75
ZNDC Line #1 Failure To Report
76
ZNDC Line #2 Failure To Report
77
ZNDC Line #1 Fault
78
ZNDC Line #2 Fault
79
ZNDC Trouble
Revision 1.0
Problem
ZNDC cannot communicate with
the Central Station.
Event Text
Part # MAN-ZNDC-01
ZNDC Installation and Operation Manual
Verify the configuration at the
Central Station. Make sure it is
using Contact ID as the reporting
format. Also make sure that it is
using the proper Handshaking and
Kissoff configurations. See section
5.2.
At the PC, make sure the phone
number to the Central Station is
correct.
At the ZNDC, listen with the
speaker to verify that the ZNDC is
dialing and making a connection.
Description
General ZNDC trouble (Network Comm Trouble,
24V Trouble, 12V Trouble, or VREF1 Trouble)
A fault was detected on line ZNDC phone line #1
A fault was detected on line ZNDC phone line #2
The ZNDC was unable to report an event on line #1
within the programmed number of attempts
The ZNDC was unable to report an event on line #2
within the programmed number of attempts
The ZNDC's programming has been lost, and reset
to factory defaults. The user needs to re-program
the ZNDC.
General ZNDC trouble restored
The fault on line ZNDC phone line #1 was restored
The fault on line ZNDC phone line #2 was restored
Description
The ZNDC was unable to report an event on line #1
within the programmed number of attempts
The ZNDC was unable to report an event on line #2
within the programmed number of attempts
A fault was detected on line ZNDC phone line #1
A fault was detected on line ZNDC phone line #2
General ZNDC trouble (Network Comm Trouble,
24V Trouble, 12V Trouble, VREF1 Trouble, or
EEPROM Corrupted)
Solution
Page 22