At The Pc; Zndc Data - Zeta ZNDC Installation And Operating Manual

Networked digital communicator
Table of Contents

Advertisement

Zeta Alarm Systems.
4 . 2
A t t h e P C
The ZNDC is programmed using the PC-based configuration program, ZNDC Programmer.
4 . 2 . 1 Z N D C D a t a
The "General Configuration" panel allows you to select:
Seconds Between Dial Attempts: If the ZNDC must make more than one attempt to reach the
central station, this parameter controls how long the ZNDC waits before trying again. Default:
5 seconds.
Maximum Handshake Time: This is the maximum amount of time the ZNDC will wait for a
handshake to be acknowledged by the Central Station. Note: generally, there is no need to
change this setting from the default. However, you might shorten it for test purposes only.
Default: 45 seconds.
Host Panel: Select either Classic 2000 Mk II or Sigma Mk II. Default: Classic 2000 Mk II.
Periodic Test Report Time: This section is used in a Sigma Mk II application.* The Sigma Mk II
panel will send out a periodic test report first at startup, and then at an appointed time later in
the day, and each following day at the same time. With this feature, the time that the periodic
test report is sent out is set at the ZNDC. Note: the time is in 24-hour mode, so 11:00 p.m.
would be 23:00.
* When the ZNDC is used with the Classic 2000 Mk II panel, the Periodic Test Report is sent when the panel
performs a self-test. The default time for the self-test is midnight; refer to the Classic 2000 Mk IIUser
Manual for further details.
Revision 1.0
ZNDC Installation and Operation Manual
Part # MAN-ZNDC-01
Page 14

Advertisement

Table of Contents
loading

Table of Contents