3 . 3 . 2 C o n n e c t i n g P o w e r a n d N e t w o r k
Connect 24VDC power and RS-485 network signals from the control panel to TB1. The pin-out of
the connector is:
Pin
1
RS-485 + In
2
RS-485 – In
3
RS-485 Shield In
4
RS-485 + Out
5
RS-485 – Out
6
RS-485 Shield Out
7
24VDC Out
8
Ground Out
9
24VDC In
10
Ground In
Pins 1, 2, 9, and 10 and required; the remainder are optional. In addition to the power connections
on TB1, also connect earth ground to J1, the metal pin located in the lower left corner of the board
(see section 3.2).
3 . 4 N e t w o r k I n s t a l l a t i o n
Note: ZNDC is hard-coded at network address 10.
3 . 4 . 1 C l a s s i c 2 0 0 0 M k I I
To install the ZNDC with a Classic 2000 Mk II FACP, connect a cable between the RS485+ and
RS485- terminals on the ZNDC to the RS485+ and RS485- terminals on the panel (terminals 17
and 18). Power the ZNDC from a 24VDC source, either the network power connections on the
panel, a NAC configured as a power supply on the panel, or an IPB-3 power booster. Once the
ZNDC is connected, power up the panel, then scan the network. The ZNDC should appear at
address 10. If it does not, then check your connections and verify that the ZNDC is configured for
Classic 2000 Mk II operation.
GND
+24V
GND
+24V
-
+
-
+
NDC
Revision 1.0
ZRM PORT
S3OOO
NETWORK WIRING DIAGRAM - S3000
ILLUS. 3.4A
Part # MAN-ZNDC-01
ZNDC Installation and Operation Manual
Function
+
-
+
-
+24V
GND +24V
17
18
19
20
21
22
23
24
GND
25
26
TO OTHER
NETWORK
DEVICES
Page 9