HKV 240 Blower Performance
All Data is Wet Coil
9000
BHP
2.98
9000
Sheave/Mtr
A
9000
RPM
653
9000
Turns Open
6
9200
BHP
3.18
9200
Sheave/Mtr
A
9200
RPM
668
9200
Turns Open
5.5
9400
BHP
3.48
9400
Sheave/Mtr
A
9400
RPM
683
9400
Turns Open
5
9600
BHP
3.68
9600
Sheave/Mtr
A
9600
RPM
698
9600
Turns Open
4.5
9800
BHP
3.88
9800
Sheave/Mtr
A
9800
RPM
715
9800
Turns Open
4.5
10000
BHP
4.08
10000
Sheave/Mtr
A
10000
RPM
730
10000
Turns Open
4
A = Standard Static/Standard Motor, B = Low Static/Standard Motor, C = High Static/Standard Motor, D = Standard Static/Large Motor, E = High Static/Large Motor
Unit factory shipped with standard static sheave and drive at 2.5 turns open. Other speed require field selection.
For applications requiring higher static pressures, contact your local representative. Performance data does not include drive losses and is based on sea level conditions.
Do not operate in black regions. All airflow in rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For dry coil performance first calculate the face velocity of the air coil (Face Velocity [FPM] = Airflow [CFM] / Face Area [sqft]). Then use preceding wet coil to dry coil conversion table.
HKV LArge CommerCiAL
Table Continued from Previous Page
3.08
3.28
3.48
3.68
A
A
A
A
679
707
731
755
5
4.5
4
3.5
3.28
3.48
3.68
3.88
A
A
A
A
694
721
745
768
5
4
3.5
3
3.68
3.78
3.88
4.08
A
A
A
A
711
735
758
782
4.5
4
3.5
3
3.88
3.98
4.08
4.28
A
A
A
A
725
749
772
795
4
3.5
3
2.5
4.08
4.28
4.48
4.68
A
A
A
A
739
762
785
810
4
3.5
3
2.5
4.28
4.48
4.68
4.88
A
A
A
A
753
776
798
822
3.5
3
2.5
2
3.88
4.08
4.18
4.28
A
A
A
A
779
804
826
848
3
2.5
2
1.5
4.08
4.28
4.48
4.68
A
A
A
A
791
816
838
860
2.5
2
1.5
1
4.28
4.48
4.68
4.88
A
A
A
C
806
828
850
871
2.5
2
1
5.5
4.48
4.68
4.88
5.08
A
A
A
E
819
836
862
883
2
1.5
1
5
4.88
4.98
5.08
5.28
A
A
E
E
831
853
874
896
1.5
1
5.5
4.5
5.08
5.28
5.48
5.68
E
E
E
E
844
865
885
908
6
5.5
5
4.5
32
Blower Performance
4.48
4.68
4.88
5.08
C
C
C
E
870
893
914
935
5.5
5
4.5
4
4.78
4.88
5.08
5.28
C
C
E
E
883
904
925
945
5
4.5
4
3.5
5.08
5.28
5.38
5.48
E
E
E
E
894
915
935
955
5
4.5
4
3.5
5.28
5.48
5.68
5.88
E
E
E
E
906
926
946
968
4.5
4
3.5
3
5.48
5.68
5.88
6.08
E
E
E
E
917
937
956
978
4.5
3.5
3
3
5.88
6.08
6.28
6.48
E
E
E
E
928
948
967
988
4
3.5
3
2.5
IOM Instructions
5.28
5.48
5.68
E
E
E
955
978
997
3.5
2.5
2
5.48
5.68
5.88
E
E
E
967
987
1007
3
2.5
2
5.68
5.88
6.08
E
E
E
977
997
1016
3
2
2
6.08
6.28
6.48
E
E
E
987
1007
1025
2.5
2
1.5
6.28
6.48
6.68
E
E
E
997
1016
1035
2.5
2
1.5
6.68
6.78
6.88
E
E
E
1007
1026
1044
2
1.5
1

Advertisement