IOM Manual HBH SERIES Heat Controller, Inc. Table of Contents Model Nomenclature ........2 Water Valve Wiring ........21 Storage............3 Thermostat Wiring ........22 Pre-Installation ..........3 Typical Wiring Diagrams ......23 Physical Data ..........5 CXM Controls ..........24 Horizontal Installation ........6 Safety Features .......... 25 Field Conversion of Air Discharge ....8...
Heat Controller OEM Price List HBH Large Compact Horizontal Units Heat Controller, Inc. HBH SERIES IOM Manual Entering Water Temperature Range: 20 - 120° F (-6. 7 - 48.9° C) Model Nomenclature Horizontal Sizes 072 - 120 HBH Large Model Structure Basic Unit Description: •...
IOM Manual HBH SERIES Heat Controller, Inc. General Information WARNING! Safety � WARNING! � Warnings, cautions and notices appear throughout this manual. Read these items carefully before attempting any WARNING! All refrigerant discharged from this unit must be installation, service or troubleshooting of the equipment.
Heat Controller, Inc. HBH SERIES IOM Manual General Information Pre-Installation - Installation, Operation, and Maintenance � CAUTION! � CAUTION! instructions are provided with each unit. Horizontal equipment is designed for installation above false ceiling or CAUTION! All three phase scroll compressors must have in a ceiling plenum.
IOM Manual HBH SERIES Heat Controller, Inc. Unit Physical Data HBH Series (60 Hz) Model Compressor Quantity Scroll Number of Circuits (Compressors) Factory Charge HFC-410a (oz) [kg] per circuit 60 [1.70] 76 [2.15] 80 [2.27] Blower Motor Blower Motor Quantity Standard Motor (hp) [kw] 1 [0.75]...
Heat Controller, Inc. HBH SERIES IOM Manual Horizontal Installation Horizontal Unit Location - Units are not designed for Mounting Horizontal Units - Horizontal units have hanger outdoor installation. Locate the unit in an INDOOR area kits pre-installed from the factory as shown in Figure 1.
Page 8
4. Electrical access is available on either side (left or right) of the front. are included on Heat Controller commercial heat pumps for the purposes of holding the filter only. For ducted return 5.
Heat Controller, Inc. HBH SERIES IOM Manual Field Conversion of Air Discharge discharge for either right or left return configuration is the WARNING! � WARNING! � same. In some cases, it may be possible to rotate the entire Step 3...
Page 10
Step 4 and access panel Remove blower panel and access panel Move motor clips to Remove 4 IOM Manual HBH SERIES Heat Controller, Inc. other side on bracket motor bolts Move motor clips to other side on bracket Step 2...
Heat Controller, Inc. HBH SERIES IOM Manual Horizontal Installation Figure 5: Right Return Side Discharge to Back Always vent the condensate line when dirt or air can collect in the line or a long horizontal drain line is required. RIGHT RETURN SIDE DISCHARGE...
If the unit is connected to existing ductwork, a previous Optional pressure-rated hose assemblies designed specifically for use with Heat Controller units are available. check should have been made to ensure that the ductwork has the capacity to handle the airflow required for the unit.
[2.9 and 4.5 l/m per kW] of cooling capacity. their tendency to leak over time. All commercial class units Heat Controller recommends 3 gpm per ton [3.9 l/m per kW] include low temperature-soldered bracket-supported IPT for most applications of water loop heat pumps. To insure water connections, which do not require a backup wrench.
IOM Manual HBH SERIES Heat Controller, Inc. Ground-Loop Heat Pump Applications Test individual horizontal loop circuits before backfilling. � CAUTION! � CAUTION! Test vertical U-bends and pond loop assemblies prior to installation. Pressures of at least 100 psi [689 kPa] should CAUTION! The following instructions represent industry be used when testing.
Page 15
Heat Controller, Inc. HBH SERIES IOM Manual Ground-Loop Heat Pump Applications HORIZONTAL INSTALLATION Figure 3: Typical Horizontal Unit Installation Figure 9: Typical Ground-Loop Application 3/8" [10mm] threaded rods (by others) Return Air Thermostat Wiring Unit Supply Air Power Flexible Duct...
IOM Manual HBH SERIES Heat Controller, Inc. Ground-Water Heat Pump Applications Expansion Tank and Pump - Use a closed, bladder-type Open Loop - Ground Water Systems - Typical open loop piping is shown in Figure 10. Shut off valves should be expansion tank to minimize mineral formation due to air included for ease of servicing.
Page 17
Heat Controller, Inc. HBH SERIES IOM Manual Water Coil Low Temperature Limit Setting - For all open loop systems the 30°F [-1.1°C] FP1 setting (factory setting- water) should be used to avoid freeze damage to the unit. See “Low Water Temperature Cutout Selection” in this manual for details on the low limit setting.
IOM Manual HBH SERIES Heat Controller, Inc. Water Quality Standards Table 3: Water Quality Standards Water Quality Closed Open Loop and Recirculating Well Parameter Material Recirculating Scaling Potential - Primary Measurement Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below pH/Calcium Hardness pH <...
Transformer - All 208/230 voltage units are factory wired for 208 volt. If supply voltage is 230 volt, installer must rewire transformer. See wire diagram for connections. Table 4a: HBH Series Electrical Data - (Standard 60Hz Units) Total Compressor Voltage...
Page 20
IOM Manual HBH SERIES Heat Controller, Inc. Electrical - Power Wiring Figure 11: TCH 072-120 Line Voltage Wiring WARNING! � WARNING! � WARNING! Disconnect electrical power source to prevent injury or death from electrical shock. CAUTION! � CAUTION! � CAUTION! Use only copper conductors for field installed electrical wiring.
See the specific unit wiring diagram for details. shown in Figure 13 to change the setting to 10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using an antifreeze solution. All Heat Controller units Low Voltage VA Ratings operating with entering water temperatures below 59°F [15°C] must include the optional water/refrigerant circuit...
IOM Manual HBH SERIES Heat Controller, Inc. Electrical - Low Voltage Wiring Figure 15: Optional Motorized Water Valve Wiring 23B0040N01 for 072 and 096 or 23B0041N01 Switch for 120 Valve Thermostat Water Solenoid Valves - An external solenoid valve(s) should be used on ground water installations to shut off flow to the unit when the compressor is not operating.
CXM control board. Practically any heat pump Position the thermostat back plate against the wall so that it thermostat will work with Heat Controller units, provided it appears level and so the thermostat wires protrude through has the correct number of heating and cooling stages.
Heat Controller, Inc. HBH SERIES IOM Manual CXM Controls DIP switch 2: Stage 2 Selection - provides selection of CXM Control - For detailed control information, see CXM Application, Operation and Maintenance (AOM) manual (part whether compressor has an “on” delay. If set to stage 2, the # 97B0003N1)).
IOM Manual HBH SERIES Heat Controller, Inc. Safety Features Safety Features – CXM Control Low pressure switch: The low pressure switch must be open and remain open for 30 continuous seconds during “on” The safety features below are provided to protect the cycle to be recognized as a low pressure fault.
Page 27
Heat Controller, Inc. HBH SERIES IOM Manual CXM Controls Unit Performance Sentinel-UPS (patent pending): The control will lockout with code 9 after 30 seconds if: UPS feature indicates when the heat pump is operating The compressor is on in the cooling mode and inefficiently.
IOM Manual HBH SERIES Heat Controller, Inc. Blower Adjustment CAUTION! Notes: � CAUTION! � Motor position should not need adjustment. Motor sheave position is at mid position of each Always disconnect all power supply(s) to unit prior to sheave. Thus the motor sheave is typically 2.5 making belt or sheave adjustments.
Heat Controller, Inc. HBH SERIES IOM Manual Tensioning V-Belt Drives General rules of tensioning 1. Ideal tension is the lowest tension at which the belt will not slip under peak load conditions. 2. Check tension frequently during the first 24-48 hours of operation.
IOM Manual HBH SERIES Heat Controller, Inc. Blower Sheave Information Table 4a: HBH Blower Sheave and Belt Information Drive Package Configuration Model Component Return/Supply Blower Sheave BK67 X 1" BK85 X 1" BK67 X 1" BK67 X 1" BK67 X 1"...
IOM Manual HBH SERIES Heat Controller, Inc. Unit Starting and Operating Conditions Table 9a: Operating Limits Operating Limits - Environment – Units are designed for indoor installation only. Never install units in areas subject Starting Limits Cooling Heating to freezing or where humidity levels could cause cabinet...
Pressurize and check the system for leaks and repair maintain loop temperatures. as appropriate. Verify that all strainers are in place (Heat Controller DO NOT use “Stop Leak” or similar chemical agent in this recommends a strainer with a #20 stainless steel wire system.
IOM Manual HBH SERIES Heat Controller, Inc. Unit Starting and Operating Conditions SYSTEM CHECKOUT CAUTION! � CAUTION! � System water temperature: Check water temperature for proper range and also verify heating and cooling set CAUTION! Do not use PVC piping. Temperatures will points for proper operation.
Heat Controller, Inc. HBH SERIES IOM Manual Unit Start-Up Procedure Unit Start-up Procedure Check air temperature drop across the air coil when 1. Turn the thermostat fan position to “ON”. Blower should compressor is operating. Air temperature drop start. should be between 15°F and 25°F [8°C and 14°C].
IOM Manual HBH SERIES Heat Controller, Inc. Unit Start-Up Procedure Figure 28: Test Mode Pins WARNING! � WARNING! � Short test pins WARNING! When the disconnect switch is closed, high together to enter Test voltage is present in some areas of the electrical panel.
Page 41
Heat Controller, Inc. HBH SERIES IOM Manual Unit Operating Conditions Operating Pressure/Temperature tables include the following notes: • Airflow is at nominal (rated) conditions; • Subcooling is based upon head pressure at compressor • Entering air is based upon 70°F [21°C] DB in heating service port;...
IOM Manual HBH SERIES Heat Controller, Inc. Preventive Maintenance important to provide consistent washing of these filters (in Water Coil Maintenance - the opposite direction of the normal air flow) once per month (Direct ground water applications only) If the system is installed in an area with a known high using a high pressure wash similar to those found at self- mineral content (125 P.P.M.
Heat Controller, Inc. HBH SERIES IOM Manual Functional Troubleshooting Fault Htg Clg Possible Cause Solution Main power Problems Green Status LED Off Check Line Voltage circuit breaker and disconnect Check for line voltage between L1 and L2 on the contactor...
IOM Manual HBH SERIES Heat Controller, Inc. Functional Troubleshooting Check G wiring at heat pump. Jumper G and R for fan Only Compressor Runs Thermostat wiring operation. Jumper G and R for fan operation. Check for Line voltage Fan motor relay across BR contacts.