Refrigerant Piping Work - Daikin FTXG09HVJU Installation Manual

R410a split series
Hide thumbs Also See for FTXG09HVJU:
Table of Contents

Advertisement

Refrigerant Piping Work

1.
Flaring the pipe end.
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward
so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.
2.
Refrigerant piping.
CAUTION
1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
[Apply oil]
Do not apply refrigeration
oil to the outer surface.
Flare nut
2-1. Caution on piping handling.
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for
bending.
2-2. Selection of copper and heat insulation materials.
• When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030 Btu/fth°F (0.035 to 0.045 kcal/mh°C))
Refrigerant gas pipe's surface temperature reaches 230°F (110°C) max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Gas side
O.D. 3/8 inch (9.5mm)
Thickness 0.031 inch (0.8mm) (C1220T-O)
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Apply refrigeration oil to the
inner surface of the flare.
Do not apply refrigeration
oil to the flare nut avoid
tightening with over torque.
Liquid side
O.D. 1/4 inch (6.4mm)
Minimum bend radius
1-3/16 inch (30mm) or more
Set exactly at the position shown below.
A
Flare tool for R410A
Die
A
[Tighten]
Torque wrench
Spanner
Piping union
Flare nut
Gas pipe thermal insulation
I.D. 0.472-0.590 inch (12-15mm)
Thickness 0.393 inch (10mm) Min.
(Cut exactly at
right angles.)
Remove burrs
Flaring
Conventional flare tool
Clutch-type
Clutch-type (Rigid-type)
0-0.020 inch (0-0.5mm)
0.039-0.059 inch (1.0-1.5mm)
Flare's inner
surface must
be flaw-free.
Flare nut tightening torque
Gas side
3/8 inch (9.5mm)
1/4 inch (6.4mm)
24.1-29.4 ft·lbf
10.4-12.7 ft·lbf
(32.7-39.9 N·m)
(14.2-17.2 N·m)
Be sure to
place a cap.
Rain
If no flare cap is
available, cover
the flare mouth
with tape to keep
dirt or water out.
Gas pipe
Gas pipe insulation
Liquid pipe insulation
Liquid pipe thermal insulation
I.D. 0.315-0.393 inch (8-10mm)
Wing-nut type (Imperial-type)
0.059-0.079 inch (1.5-2.0mm)
Check
The pipe end must
be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.
Liquid side
Wall
Inter-unit wiring
Drain hose
Insulation tape
Liquid pipe
■English 11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ftxg15hvjuFtxg12hvju

Table of Contents