Refrigerant Piping Work

1.

Installing outdoor unit

1) When installing the outdoor unit, refer to "Precautions for Selecting the Location" on page 3 and the "Indoor/Outdoor Unit
Installation Drawings" on page 4.
2) If drain work is necessary, follow the procedures below.
2.

Drain work

1) Use the drain plug for drainage.
2) If the drain port is covered by a mounting base or floor surface, place addi-
tional foot bases of at least 30mm in height under the outdoor unit's feet.
3) In cold areas, do not use a drain plug and drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating performance.)
3.
Refrigerant piping
CAUTION
• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R32.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
• Do not reuse joints which have been used once already.
• Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In
Europe the EN378 is the applicable standard that shall be used.
• Ensure that the field piping and connections are not subjected to stress.
Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
Flare nut tightening torque
Flare nut for Ø6.4
Flare nut for Ø9.5
Flare nut for Ø12.7
7
[Apply oil]
Do not apply refrigeration
oil to the outer surface.
Flare nut
Do not apply refrigeration oil to
the flare nut to avoid tightening
with excessive torque.
14.2-17.2N
m
(144-175kgf
cm)
3/8 inch
32.7-39.9N
m
32.7-39.9N
(333-407kgf
(333-407kgf
cm)
49.5-60.3N
m
(505-615kgf
cm)
Bottom frame
Drain plug
Hose (available commercially,
inner dia. 16mm)
Apply refrigeration oil to
the inner surface of the
flare.
Valve cap tightening torque
Gas side
1/2 inch
m
48.1-59.7N
m
21.6-27.4N
(220-280kgf
cm)
(490-610kgf
cm)
Service port cap tightening torque
10.8-14.7N
m (110-150kgf
cm)
Drain-water hole
Liquid side
1/4 inch
m
cm)