For successful installation and operation of the switch, ensure that the following environmental requirements are
met:
Because the Brocade VDX 6720 switches can be ordered with fans that move air either front to back or back to
front, be sure to orient your switch with the airflow pattern of any other devices in the rack. All equipment in the
rack should force air in the same direction to avoid intake of exhaust air.
A maximum of 102 cubic meters/hour (60 cubic feet/minute) and a minimum of 74.8 cubic meters/hour
(44 cubic feet/minute) of air flow is available to the air intake vents.
The ambient air temperature does not exceed 40

Rack considerations

For successful installation and operation of the switch in a rack, ensure the following rack requirements are met:
The rack must be a standard EIA rack.
The rack space required is one or two rack units high depending on the switch ordered (1U for the Brocade VDX
6720-24 or 2U for the Brocade VDX 6720-60); 4.3 cm (1.7 in.) or 8.90 cm (3.50 in.) high and 42.9 cm (16.9 in.)
wide.
The equipment in the rack is grounded through a reliable branch circuit connection and maintains ground at all
times. Do not rely on a secondary connection to a branch circuit, such as a power strip.
Airflow and temperature requirements are met on an ongoing basis, particularly if the switch is installed in a
closed or multirack assembly.
The additional weight of the switch does not exceed the rack's weight limits or unbalance the rack in any way.
The rack is secured to ensure stability in case of unexpected movement, such as an earthquake.
4 of 12
Value
250 watts, 4 amps, 12 VDC - VDX 6720-24
500 watts, 7 amps, 12 VDC - VDX 6720-60
146.2 W - VDX 6720-24
360 W - VDX 6720-60
Idle: 182.4 W
Maximum: 306 W
Idle: 206 W
Maximum: 306 W
85-264 VAC
47-63 Hz
1044.11 BTU/hr
Maximum of 50A
AC lines are fused
°
°
C (104
F) while the switch is operating.
Brocade VDX 6720 QuickStart Guide