9.3
Power Range 6000 VA (208/240 V)
Rackmount
General
Topology
Certifications
Input
Voltage (V)
Capacity (VA)
Frequency
Frequency Synchronization
Power Factor
Current THD
Cold Start (0 to 100% load)
Earth leakage (max.)
Bypass
Voltage (V)
Output
Voltage
Voltage Regulations
Capacity (W)
Frequency
Battery Mode/Free Run Mode
Wave Form
Load Power Factor
Efficiency AC/DC/AC
High Efficiency Mode Efficiency
Rated Current (based on 240V)
Inverter Overload Capacity
Crest Factor
Voltage Transient Response
(battery mode with R type load)
Voltage Transient Recovery (R
type Load)
On-line Transfer Time – Inverter to
Bypass and Bypass to Inverter
High Efficiency Transfer Time –
Inverter to Bypass and Bypass to
Inverter
Short Circuit Protection
Voltage Total Harmonic Distortion
(Full Linear Load)
Voltage Total Harmonic Distortion
(Full Non-Linear Load)
Steady State Output Voltage
Regulation
Common Mode Noise
Leakage Current
Surge Protection
1000 Series 6kVA Specification
Specification
US 208/240V
True on-line, Double conversion, IGBT Power Factor Correction
Input
CE
Single Phase - 208/240Vin
6kVA
45-65 Hz auto sensing
± 3Hz
Greater than 0.97
Less than 15%
Default Output Frequency 60 Hz
2mA (UPS only)
+10/-15% of nominal (default)
+10/-10% of nominal
+15/-20% of nominal
Set by display panel
208V or 240V
± 3%
4.2kW
50 / 60 Hz auto sensing
± 0.25 Hz
Sine wave, zero transfer time
0.7 PF
Greater than 89% at Nominal Voltage
Greater than 92%
25.0
125% for 1 min, 150% for 10 sec
3.0 at full load
0%100%0%; ± 15 % max.
20%100%20%; ± 9 % max.
Return to nominal voltage within 30 ms
Less than 4m sec
Less than 4m sec transfer time
Electronic overload and short circuit.
Less than 3 % THD
Less than 5 % THD
No-load to Full-load +/- 2% at full battery.
less than 0.5Vrms
.5mA
MOV 260 Jules on Output
UT1G1G060C6RKB3 + UT1-BR-0607
31