Toshiba 1000 SERIES User Manual page 36

Hide thumbs Also See for 1000 SERIES:
Table of Contents

Advertisement

2400VA Power Wiring Options
The 2400VA unit is hardwired Input and Output only. Use the following wiring
guidelines.
Note – Use minimum No. 14 AWG or 1.5 mm2, 60°C copper wire and 22 Lb-in Torque
force when connecting to Input and Output connection.
1.
X1-X3 – 240V – FULL LOAD
I/L
L1
I/N
L2
G
240
120
X1
88
X2
Load MAX 100%
N
0
120
X3
G
Terminal Block
2.
X2-X3 – 208V – FULL LOAD
I/L
L1
I/N
L2
G
120
X1
88
208
X2
0
N
Load MAX 100%
0
120
X3
G
Terminal Block
3.
X1-N or N-X3 – 120V – HALF LOAD
I/L
L1
I/N
L2
G
120
120
X1
88
Load MAX 50%
X2
0
0
N
120
X3
G
Terminal Block
120
240
88
0
0
0
O/P
120
ISO
0
OPISO
120
240
88
0
0
O/P
120
ISO
0
OPISO
120
240
88
0
0
O/P
120
ISO
0
OPISO
0
Load MAX 50%
120
Terminal Block
11
I/L
L1
I/N
L2
G
120
120
240
X1
88
88
0
X2
0
0
N
O/P
120
120
X3
ISO
0
G
OPISO

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents