Mitsubishi Electric MUH-GA35VB Service Manual page 5

Split-type, heat pump air conditioners, wireless type models
Hide thumbs Also See for MUH-GA35VB:
Table of Contents

Advertisement

2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe.
For details of flaring work, refer to Installation manual "FLARING WORK".
Pipe diameter
mm
6.35
9.52
3.Refrigeration oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
• Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder.
If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the
outdoor unit. In this case, ability of the refrigeration cycle decreases or normal operation can be impossible. However,
charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
Indoor unit
Refrigerant gas
cylinder
operating valve
Dimension of flare nut
R410A
17
22
Union
Liquid pipe
Gas pipe
Service port
Gauge manifold
valve (for R410A)
Charge hose (for R410A)
Refrigerant gas cylinder
for R410A with siphon
Refrigerant (liquid)
Electronic scale for refrigerant charging
5
R22
17
22
Stop valve
Outdoor unit

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Muh-ga20vbMuh-ga25vb

Table of Contents