Troubleshooting Flow - Mitsubishi Electric MUH-GA35VB Service Manual

Split-type, heat pump air conditioners, wireless type models
Hide thumbs Also See for MUH-GA35VB:
Table of Contents

Advertisement

10-3.
Trouble criterion of main parts
MUH-GA20VB -
E1
Part name
Measure the resistance with a tester.
(Part temperature –10°C ~ 40°C)
Defrost
thermistor
(RT63)
Compressor
Measure the resistance between the terminals with a tester.
(MC)
(Coil wiring temperature –10°C ~ 40°C)
INNER
PROTECTOR
MUH-GA20/GA25VB
150i 5°C OPEN
90i10°C CLOSE
C-R
MUH-GA35VB
155i 5°C OPEN
C-S
90i10°C CLOSE
Measure the resistance between the terminals with a tester.
Outdoor fan
(Coil wiring temperature –10°C ~ 40°C)
motor
(MF)
INNER FUSE
145i 2°C
CUT OFF

10-4. Troubleshooting flow

Compressor and/or outdoor fan motor doesn't operate.
A A Check of outdoor unit
Start
Is the switch SW2-2 on the
indoor electronic control
P.C. board set to MUH type?
Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch.
3-minute time delay works.
Test run operation operates for 30 minutes.
Compressor
doesn't operate.
Is there 5V DC between J205
the deicer P.C. board?
Is there 230V AC between 3 on the
compressor contactor (52C) and N
on the outdoor terminal block (TB1)?
Check the compressor and compressor
capacitor, and rectify the connecting wire.
Outdoor fan motor
doesn't operate.
Is there 5V DC between J205
the deicer P.C. board?
Check the outdoor fan motor
and rectify the connecting
wire.
MUH-GA25VB -
E1
Check method and criterion
Normal
5kΩ ~ 60kΩ
Normal
MUH-GA20VB
MUH-GA25VB MUH-GA35VB
3.41~4.18Ω
2.99~3.67Ω
5.41~6.63Ω
4.02~4.92Ω
Color of
lead wire
MUH-GA20VB
323 ~ 396 Ω
WHT-BLK
241 ~ 296 Ω
BLK-RED
Change the switch SW-2-2
No
on the indoor electronic control
P.C. board to MUH type.
Yes
No
+
–J101
on
Yes
Replace the
No
deicer P.C.
board.
Yes
No
+
–J101 on
Yes
MUH-GA35VB -
E1
Abnormal
Open or short-circuit
Abnormal
2.46~3.01Ω
Open or short-circuit
2.96~3.63Ω
Normal
MUH-GA25/GA35VB
189 ~ 233 Ω
270 ~ 332 Ω
Is there 230V AC between 4 on the
compressor contactor (52C) and
TAB20 on the deicer P.C. board?
Yes
Replace the
deicer P.C. board.
Is there 230V AC between 4 on the
compressor contactor (52C) and
TAB 20 on the deicer P.C. board?
Yes
Replace the
deicer P.C. board.
24
Abnormal
Open or short-circuit
Rectify the indoor and
outdoor connecting wire.
No
Is there 230V AC between L–N
on the outdoor terminal block (TB1)?
Yes
Rectify the connecting wire.
Rectify the indoor and
outdoor connecting wire.
No
Is there 230V AC between L–N on
the outdoor terminal block (TB1)?
Yes
Rectify the connecting wire.
Figure
WHT
C
P
AUX.
MAIN
S
R
BLK
RED
MAIN
AUX.
FUSE
BLK
RED
WHT
P INNER PROTECTOR
No