Service Functions; Troubleshooting - Mitsubishi Electric MUH-GA35VB Service Manual

Split-type, heat pump air conditioners, wireless type models
Hide thumbs Also See for MUH-GA35VB:
Table of Contents

Advertisement

9

SERVICE FUNCTIONS

MUH-GA20VB -
E1
MUH-GA25VB -
E1
MUH-GA35VB -
E1
9-1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JPDS and JPSG on the outdoor deicer P.C. board, defrosting mode can be accom-
plished regardless of the defrost interval restriction. (Refer to 10-5.)
Defrost thermistor RT61 must read below -3°C.
9-2. CHANGE IN DEFROST SETTING
<JRF> When the JRF wire of the deicer P.C. board is cut, the defrost interval time will be changed.
<JRG> When the JRG wire of the deicer P.C. board is cut, the defrost temperature will be changed.(Refer to 10-5.)
MODEL
MUH-GA20VB -
E1
MUH-GA25VB -
E1
MUH-GA35VB -
E1
10

TROUBLESHOOTING

MUH-GA20VB -
E1
MUH-GA25VB -
E1
MUH-GA35VB -
E1
10-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to turn off the main unit first with the remote controller, and then after con-
firming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
3) When troubleshooting, refer to 10-2. "Instruction of troubleshooting".
Jumper wire
Defrost interval time changes from 40 minutes to 15 minutes.
JRF
JRG
Deforst start temperature changes from -3: to 0:.
Housing point
Lead wiring
Change point
22