8. Charging Compressor Oil
(2) Charging compressor oil into oil-charging tank
Connect a piece of pipe to the lower valve and then insert the other end deeply into the bottom of the oil con-
tainer. Make sure you avoid letting any air be sucked into the tube. Next, run the vacuum pump and open the
manifold gauge valves, then open the upper and lower valves to begin charging oil into the charging tank.
Vacuum pump
When the predetermined amount of oil has been charged into the oil-charging tank, immediately close the lower
valve. Next, run the vacuum pump until the system pressure reaches lower than -14.7 psig (5 Torr).
Close the upper valve and then, stop the vacuum pump.
Do this operation quickly because compressor oil easily absorbs moisture from
CAUTION
the air.
(3) Charging compressor oil into outdoor unit
Connect the lower valve to the low-pressure outlet (with Schrader-type push-to-release valve) in the outdoor
unit to be oil-charged, and then connect the high-pressure outlet (with push-to-release valve) to the upper valve
via the manifold gauge valves (at Hi-pressure gauge side). In addition, connect the gas tube service port (with
push-to-release valve) to the DPR (Discharge Pressure Regulator). Carry out the connection work quickly to
avoid letting air enter.
• The hoses may be subject to internal pressure from the refrigerant inside the out
CAUTION
• Since the DPR valve opens at pressures of 362.6 psi and above, be sure to con-
High-pressure
outlet port
(For 5/16"
(7.94mm)-
dia. connector)
Manifold
gauge
door unit. A Schrader-type push-to-release valve is provided at each connection
port.
nect the DPR to the gas tube service port (low-pressure side).
Low-pressure
outlet port
(For 5/16"
(7.94mm)-
dia. connector)
Gas tube
service port
(For 5/16"
(7.94mm)-
dia. connector)
Close
Upper valve
Close
Lower valve
Fig. 16
Upper valve
Manifold
gauge
Lo
Hi
Lower valve
Fig. 17
2 - 17
W-2WAY ECO-i SYSTEM
Outdoor Unit Repair Procedures
Open
Open
Oil
DPR