Pressure Sensor Failure - Sanyo CHDXR09663* Service Manual

2-way eco-i multi system
Hide thumbs Also See for CHDXR09663*:
Table of Contents

Advertisement

15. Pressure Sensor Failure

This system contains 2 types of pressure sensors: a high-pressure sensor and a low-pressure sensor.
(1)
High-pressure sensor failure
Alarms are emitted when the high-pressure sensor becomes an electrical open-circuit or a short-circuit condi-
tions, and a broken wiring, short-circuit or poor connection to the PCB in the high-pressure sensor circuit.
(2)
Low-pressure sensor failure
Alarms are emitted when the low-pressure sensor becomes an electrical open-circuit or a short-circuit condi-
tions, and a broken wiring, short-circuit or poor connection to the PCB in the low-pressure sensor circuit.
Alarm display
High-pressure sensor failure
F16
1 - 27
W-2WAY ECO-i SYSTEM
Control Functions
Low-pressure sensor failure
F17
1