Honeywell VISTA 15P - Ademco 6 Zone Control Panel Installation And Operation Manual page 36

Ademco vista series
Hide thumbs Also See for VISTA 15P - Ademco 6 Zone Control Panel:
Table of Contents

Advertisement

Installation and Setup Guide
Entry Delay No. 1 and No. 2 (fields ∗ 35, ∗ 36) cannot be greater than 30 seconds for UL Residential
1.
Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL
Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.
2.
For UL Commercial Burglar Alarm and UL Residential Burglar Alarm installations with line
security, total exit delay time must not exceed 60 seconds.
The maximum number of reports per armed period (field ∗ 93) must be set to "0" (unlimited) for UL
3.
installations.
4.
Periodic testing (see scheduling mode) must be at least every 24 hours.
5.
Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations
(Aux power 500mA max.).
6.
All partitions must be owned and managed by the same person(s).
7.
All partitions must be part of one building at one street address.
8.
If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.
9.
For UL commercial burglar alarm installations the control unit must be protected from
unauthorized access. The tamper switch installed to protect the control unit enclosure door is
suitable for this purpose.
10. Remote downloading without an alarm company technician on-site (unattended downloading) is not
permissible for UL installations.
11. Auto-disarming is not a UL Listed feature.
12. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and
residential applications, the following UL requirements per UL681 are provided:
The maximum time that a control unit shall be programmed to delay the transmission of a signal to
a remote monitoring location, or to delay the energizing of a local alarm sounding device to permit
the alarm system user to enter and disarm the system, or to arm the system and exit shall not
exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.
13. This control is not intended for bank safe and vault applications.
1.
*31 Single Alarm Sounding per Zone: If "0" selected, "alarm sounding per zone" will be the same as
the "number of reports in armed period" set in field *93 (1 if one report, 2 if 2 reports, unlimited for
zones in zone list 7).
2.
*34 Exit Delay: Minimum exit delay is 45 seconds.
3.
*35/*36 Entry Delay 1 and 2: Minimum entry delay is 30 seconds.
4.
*37 Audible Exit Warning: Feature always enabled; field does not exist.
5.
*39 Power Up in Previous State: Must be "1," power up in previous state.
6.
*40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting disable option
in field *91 must be set.
7.
*50 Burglary Dial Delay: Delay must be a minimum of 30 seconds.
8.
*59 Exit Error Alarm Report Code: Always enabled.
9
*68 Cancel Report Code: Default is "code enabled."
10. *69 Recent Closing Report Code: Always enabled.
11. *91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting
Disable must be set to "1" (enabled).
12. *93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.
13. Cross zone timer programming is set in field ∗85; cross zone pairs are assigned in zone list 4 using
∗81 Zone List mode.
14. Duress code is assigned by using the "add a user code" procedure found in the User Guide. Enable
Duress code reporting by programming zone 92 using ∗56 Zone Programming mode.
15. Fire alarm verification is a built-in system feature when a zone is programmed for zone type 16.
6-2
UL NOTICES
SIA Quick Reference Guide