Table GD-1 — General Data
Cooling Performance
1
Gross Cooling Capacity
EER
2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
3
Integrated Part Load Value
System Power KW
Heating Performance
1
High Temp. Btuh Rating
System Power KW/COP
Low Temp. Btuh Rating
System Power KW/COP
HSPF (Btu/Watts-hr)
Compressor
No./Type
ARI Sound Rating (BELS)
4
Outdoor Coil — Type
Tube Size (in.) OD
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Indoor Coil — Type
Tube Size (in.)
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan — Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
CFM
No. Motors/HP
Motor RPM
Indoor Fan — Type
No. Used
Diameter x Width (in.)
Drive Type/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
6
Filters — Type Furnished
(No.) Size Recommended (in.)
5
Refrigerant Charge (Lbs of R-22)
Notes:
1. Cooling Performance and Heating Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat.
ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ASHRAE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 340. Units are rated at 80°F entering dry bulb, and 67°F entering wet bulb at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Optional 2 inch pleated filter also available.
*Indicates both downflow and horizontal units.
12
General
Data
12½ Ton Downflow and Horizontal Units
WCD150B3, B4, BW
WCH150B3, B4, BW
152,00
152,000
9.5
4,400 / 4,400
4,400 / 4,400
144,000
144,000
9.9
15.16
135,000
132,000
12.76/3.10
12.48/3.10
78,000
10.88/2.1
10.55/2.0
2/Scroll
2/Scroll
9.2
Hi-Performance
Hi-Performance
.375
23.96
2/16
Expansion Valve
Expansion Valve
Hi-Performance
Hi-Performance
.375
15.83
2/15
Capillary Tube
Capillary Tube
1/1.00 NPT
1/1.00 NPT
Propeller
Propeller
2/26
Direct/1
Direct/1
10,800
2/.50
1,110
FC Centrifugal
FC Centrifugal
1
15 x 15
15 x 15
Belt/1
1
3.0/5.0
1,740/3,450
1,740/3,450
145T/145T
145T/145T
Throwaway
Throwaway
(2) 20 x 20 x 2
(2) 20 x 20 x 2
(4) 20 x 25 x 2
(4) 20 x 25 x 2
11.1/11.4 Circuit
11.5/11.8 Circuit
(12½ Ton)
9.5
9.9
15.16
72,000
9.2
.375
23.96
2/16
.375
17.50
2/15
2/26
10,800
2/.50
1,110
1
Belt/1
1
3.0/5.0