STINGER Specifications

Compatible
Refrigerants
Power
Compressor
Cooling
Protection
Pressure Ratings
Temperature
Case
Size / Weight
Certification
Refrigerant
Liquid Rate
3.53 lb/min
R-22
1.60 kg/min
2.67 lb/min
R-134A
1.21 kg/min
3.02 lb/min
R-410A
1.37 kg/min
STINGER
R-12, R-22, R-114, R-134a, R-401A, R-401B, R-401C, R-402A,
R-402B, R-404A, R-406A, R-407A, R-407B, R-407C, R-407D,
R-408A, R-409A, R-410A, R-411A, R-411B, R-412A, R-500,
R-502, R-507, R-509
• 110/120 VAC, 1 Phase, 50/60 Hz, 8 Amps
• 220 VAC, 1 Phase, 50/60 Hz, 4 Amps
¾ HP High Performance Oilless
Two Cooling Fans
High pressure cutoff at 550 psi. Compressor is protected by
circuit breakers and internal compressor thermal sensor.
Optional 80% tank full shutoff kit (P/N 2090-0091).
Low Side design pressure 450 PSI
High Side design pressure 550 PSI
Operating Range 32 to 104 °F (10 to 40 °C)
Blow-Molded, High Impact Polyethylene
Length
17"
Width
9.5"
Height
11"
Weight
24 Lbs.
Complies with UL1963 (not evaluated for automotive use)
Refrigerant Recovery Rates
Certified per ARI 740-95 & 740-98
Liquid Push-Pull
Rate
12.30 lb/min
5.58 kg/min
10.98 lb/min
4.98 kg/min
14.62 lb/min
6.63 kg/min
Vapor Rate
0.29 lb/min
0.13 kg/min
0.22 lb/min
0.10 kg/min
0.22 lb/min
0.10 kg/min
3
See label on
back of unit
Vacuum Level
(inches Hg)
>15
>15
>15

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the High Performance Oilless Commercial Refrigerant Recovery Unit and is the answer not in the manual?

Subscribe to Our Youtube Channel

Related Products for Bacharach High Performance Oilless Commercial Refrigerant Recovery Unit

This manual is also suitable for:

Stinger

Table of Contents