Installation

Utility Closet Dimensions

Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 3. Three inches minimum clearance
on three sides of the unit must be allowed for return airflow, installation access and service access. See Figures 3 & 4 for clearances
and reference dimensions.
Figure 3
Typical Utility Closet
Field-supplied
Filter (25" x 20")
VPRG4 Access Panel &
Return Air Filter Grille
Vert-I-Pak Chassis 2-ton dimensions:
23 1/8" wide x 23 1/8" deep x 47 1/4" high.
See Figure 16, page 14 for proper chasis
installation.
NOTICE
Drain pan must be installed in closet prior to chassis
insertion into plenum. See Page 10 for drain pan insta-
llation details. Failure to do so can result in property
damage.
58"
Power
Disconnect
29"
Recommended field
installed drain pan
Optional Platform
3" Clearance on all
three sides minimum for
service and installation
Chassis Shown in Closet, on Optional Platform
Rigid Ductwork
Exterior Wall
Flexible Ductwork
VPAWP1-8/1-14Wall Plenum
VPDP1 drain pan beneath
unit is required on all
Chassis is
VEA/VHA24 units. Drain
shipped with
pan must be installed prior
vibration
to chassis installation
isolators
installed
Figure 4
control box
electrical
entrance
Plenum
Top View
5