Factory Presets - Trane IntelliPak CGAF Series Programming, Troubleshooting Manual

Air-cooled cold generator, "h" and later design sequence, with 3-dtm scroll compressors
Table of Contents

Advertisement

Factory Presets

The CGM controlled unit has many operating functions
whose settings are preset at the factory, but may be modi-
fied to meet the unique requirements of each job. The fol-
lowing list identifies each of the unit's adjustable functions
and the value assigned to it. If these factory presets match
your application's requirements and the"System Start-Up
procedures in the Installation, Operation & Maintyenance
manual has been completed, simply press the AUTO key at
the Human Interface module to begin unit operation.
Setpoints
Leaving Solution Setpoint
Low Ambient Compressor Lockout
Temperature Setpoint
Heat Tape Temperature Setpoint
Hot Start Load Limit Setpoint
Ice Building Terminate Temperature
Low Solution Cutout Temperature
Low Ambient Pump Override Temperature
Use Leaving Solution Setpoint From:
Use Ice Building Terminate Setpoint From:
Use Hot Start Load Limit Setpoint From:
Use Capacity Limit Setpoint From:
Information format
Display Text in
Display Units in
Unit Control
Unit Address
General Unit Functions Setup
Delay unit Start
Demand Limit Definition
Hot Gas Bypass Function
Hot Gas Bypass Max Run Time
Hot Start Time Interval
Hot Operation Response Option
Pumpdown Function
Compressor Lead/Lag Function
Default Chiller Solution Pump Mode
Evaporator Solution Pump Off Delay Time
Loop Stabilization Time
Low Ambient Compressor Lockout
Leaving Solution Reset Type
Chiller Application
Evaporator Solution Flow Switch Proving
OA Temp Reset Type: Start Temp
OA Temp Reset Type: End Temp
OA Temp Reset Type: Max Amount of Reset
Zone Temp Reset Type: Start Temp
Zone Temp Reset Type: End Temp
Zone Temp Reset Type: Max Amount of Reset
Entering Solution Temp Reset Type: Start Temp
Entering Solution Temp Reset Type: End Temp
Entering Solution Temp Reset Type: Max Amount
General Information
If your application requires different settings, turn to the
listed page beside the function, press the designated func-
tion menu key, then press and hold the NEXT or PREVI-
OUS key until its screen appears on the LCD. Once the
proper screen appears, simply follow the programming in-
structions given below the applicable screen in this manual.
Note: Record any changes made to the factory
preset values in the corresponding space provided.
Factory Preset
Changed
44 deg F
40 deg F
40 deg F
71 deg F
27 deg F
35 deg F
35 deg F
HI STP Menu
HI STP Menu
HI STP Menu
No Source Selected
English Language
English
Local
49
0 Seconds
None
Disabled
30 Minutes
60 Minutes
50% Capacity
(Auto Reset Diag.)
Disabled
Disabled
Auto
30 Seconds
120 Seconds
Enabled
None
Comfort
Disabled
70 deg F
50 deg F
5 deg F
78 deg F
75 deg F
5 deg F
45 deg F
40 deg F
5 deg F
12
See page...
To
to adjust
34
SETPOINTS
34
SETPOINTS
34
SETPOINTS
34
SETPOINTS
34
SETPOINTS
34
SETPOINTS
34
SETPOINTS
34
SETPOINTS
34
SETPOINTS
35
SETPOINTS
35
SETPOINTS
23
23
23
23
23
24
24
24
24
24
24
24
24
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
To adjust
Press....
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP
SETUP